Sagi KBS16A (внутренний агрегат) [20/73] Alarms and signals

Sagi KBS16A (внутренний агрегат) [20/73] Alarms and signals
9
A2 0 2 - 1
kind of lower temperature alarm
0=alarm not enabled
1=relative to the working setpoint (or "working setpoint - A1”; consider A1 without sign)
2=absolute (or A1)
A4 -99 99 °C/°F (1) 15
temperature above which the upper temperature alarm is activated; also look at A3 and
A5 (4)
A5 0 2 - 1
kind of upper temperature alarm 0=alarm not enabled 1=relative to the working setpoint
(or "working setpoint + A4”; consider A4 without sign) 2=absolute (or A4)
A6 0 240 min 120 upper temperature alarm delay since you turn on the instrument (only if A3 = 0)
A7 0 240 min 15 temperature alarm delay
A8 0 240 min 60
upper temperature alarm delay since the end of the after dripping evaporator fan delay
(only if A3 = 0)(12)
LABEL MIN. MAS. U.M. DEF. EVAPORATOR FAN
F0 0 4 - 1
evaporator fan activity during the normal operation
0=turned off
1=turned on
2=according to the compressor
3=according to F1 (14)
4=turned off if the compressor is turned off, according to F1 if the compressor is turned on (14)
F1 -99 99 °C/°F (1) -1 evaporator temperature above which the evaporator fan is turned off (only if F0 = 3 or 4) (4)
F2 0 2 - 0
evaporator fan activity during the defrost and the dripping
0=turned off
1=turned on
2=according to F0
F3 0 15 min 3 duration of the after dripping evaporator fan delay
LABEL MIN. MAS. U.M. DEF. SERIAL NETWORK (MODBUS)
LA 1 247 - 1 instrument address
Lb 0 3 - 2
baud rate
0=2.400 baud
1=4.800 baud
2=9.600 baud
3=19.200 baud
LP 0 2 - 2
Parità
0=none
1=odd
2=even
(1) the unit of measure depends on parameter P2
(2) set the parameters related to the regulators appropriately after the modification of the parameter P2
(3) if parameter C1 has value 0, the delay since the end of the cabinet probe error will however be 2 min
(4) the differential of the parameter is 2.0 °C/4 °F
(6) the instrument stores the count of the defrost interval every 30 min; the modification of parameter d0 has effect since the end of the previousdefrost
interval or since the activation of a defrost by hand
(7) the display restores the normal operation as soon as the after dripping evaporator fan delay ends and the cabinet temperature falls belowthe one that has
locked the display (or if a temperature alarm arises)
(8) if parameter P3 has value 0 or 2, the instrument will work as if parameter d8 had value 0
(9) if (to the defrost activation) the duration of the activation of the compressor is shorter than the time you have set with parameter dA, thecompressor will
further remain turned on the fraction of time required to complete it
(10) if parameter P3 has value 0, the instrument will work as if parameter A0 had value 0
(12) during the defrost, the dripping and the evaporator fan delay the temperature alarms are not enabled, on condition that they have arisenafter the
activation of the defrost
(14) if parameter P3 has value 0, the instrument will work as if parameter F0 had value 2
LOADING THE PRODUCT
Distribute the product evenly inside the refrigerated
compartments so as to allow adequate air circulation;
Do not obstruct the ventilation areas of the cooling
system located on the left of the compartment;
Do not use the lower drawer on the right to store
foodstuffs requiring low-temperature storing;
Cover or wrap foodstuffs with specific protective films
before storing;
Do not introduce hot foodstuffs or beverages;
Do not leave the door open longer than is necessary
when introducing or removing products.
STOPPING
To stop operation at any time, position the main switch on
OFF. The button turns off.
To disconnect the counter from the power supply, remove the
plug from the outlet.
DEFROSTING
The defrosting of the appliances is completely automatic and it
is carried out through electric resistance and operated by a
thermoregulator.
The defrosting occurs automatically every 6 hours. The
duration of the defrosting is automatically regulated by the
refrigerator.
A defrost cycle can be selected at any time by pressing button
”(see fig. e) for 5 seconds.
At the end of the manual defrosting cycle, the automatic
defrosting mode is restored.
The appliance is supplied with an automatic evaporation
control for the condensed steam.
ALARMS AND SIGNALS
Alarms must be silenced by the “
” key.
Any alarm and signalling are visualized on the display: