9. Installing the grille
9.4.2. Temporary installation of the grille (Fig. 9-6)
• Temporarily secure the grille using the bell shaped holes by putting the socket of
the grille marked
G
on the corner drain pipe area of the main unit.
*
Make sure that the lead wiring of the grille does not get pinched between the
grille and the main unit.
9.4.3. Securing the grille (Fig. 9-7)
• Secure the grille to the main unit by tightening the previously installed 2 screws
(with captive washer) as well as the 2 remaining screws (with captive washer).
*
Make sure that there are no gaps between the main unit and the grille or the
grille and the ceiling.
Fixing gaps between the grille and the ceiling
With the grille attached, adjust the height of the main unit to close the gap.
Caution:
When tightening the screw with captive washer
2
, tighten it at a torque of 4.8
N•m or less. Never use an impact screwdriver.
•
It may result in parts damage.
9.4.4. Wire connection (Fig. 9-8)
• Remove the 2 screws fixing the cover of electrical branch box of the unit and
open the cover.
• Be sure to connect the connector(white, 20-pole) for vane motor of the grille to
CNV connector of controller board of the unit.
• As for PLP-6BALM(E), the connector of wireless sensor cable is also connected
to connecor CN90 on indoor controller board.
The lead wire of grille is passed through the catch of bell mouth of the unit
perfectly. The remaining lead wire is tied with clamp of the unit and put the cover of
the unit again with 2 screws.
Note:
Do not put the remaining lead wire in electrical branch box of the unit.
9.5. Installing the intake grille (Fig. 9-9 )
Note:
When reinstalling the corner panels (each with a safety wire attached), con-
nect the other end of each safety wire to the grille using a screw (4 pcs,
4×8) as shown in the illustration.
*If the corner panels are not attached, they may fall off while the unit is operating.
• Perform the procedure that is described in “9.2. Preparing to attach the grille” in
reverse order to install the intake grille and the corner panel.
• Multiple units can be installed with grille so that the position of the logo on each
corner panel is consistent with the other units regardless of the orientation of the
intake grille. Align the logo on the panel according to the wishes of the customer
as shown in the diagram to the left. (The position of the grille can be changed.)
D
Refrigerant piping of the main unit
E
Drain piping of the main unit
F
Initial position of the corner panel(logo attached)
* Installation in any position is possible.
G
Initial position of the levers on the intake grille
* Although the clips can be installed in any of 4 positions, the conguration shown
here is recommended.(It is not necessary to remove the intake grille when
maintenance is performed on the electric component box of the main unit.)
H
Receiver (Only PLP-6BALM, PLP-6BALME Panel)
I
i-see sensor(PLP-6BAE, PLP-6BAMDE, PLP-6BALME panel)
9.6. Installation of i-see sensor corner panel
(Fig. 9-10)
For PLP-6BAE, PLP-6BAMDE, PLP-6BALME panel
• Take the lead wires CN4Y(white) and CN6Y(red) of the i-see sensor corner panel
8
from the side of the electrical box on the unit and make sure to conect them to
the connector of the controller board.
•
Lead wires of the i-see sensor corner panel
8
should be xed at the rib of the
grille with the fastener
4
so that there is no slack.
•
Lead wires should be held together with the lead wires of the unit and xed with 2
of the fastener
4
so that there is no slack.
•
Put the cover back on the electrical box with 3 screws.
* Make sure wires are not caught in the cover of electric box. If they are caught,
they will be cut.
•
Adverse procedure of “9.2. Preparing to attach the grille” will be taken for install-
ing the i-see sensor corner panel.
* The i-see sensor corner panel should be xed onto the grille
1
with screw
6
.
A
Main unit
C
Corner drain pipe area
D
Screw with washer
2
(for temporary use)
E
Grille
F
Screw with washer
2
G
Socket
H
Bell shaped hole
Fig. 9-6
A
Ceiling
B
Main unit
C
Grille
D
Make sure that there are no gaps.
E
A
djust the nut of the main unit using a
wrench, etc.
A
Clamp of the main unit
B
Electrical box
C
Indoor controller board
D
Catch for bell mouth
E
Lead wire of grille
Fig. 9-7
A
Screw (4×8)
5
B
Corner panel
C
Safety wire
(Enlarged)
Fig. 9-8
Fig. 9-9
Fig. 9-10
A
Controller board CN4Y
B
Controller board CN6Y
C
2 fasteners
4
D
Fastener
4
E
i-see sensor corner panel
8
F
Rib for grille
G
Screw
6
01_BH79D045K08_EN.indd 18 2014/02/13 13:21:05
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Pla rp ba series pla zrp ba series pla sp ba series 1
- Português 1
- Svenska 1
- Türkçe 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Ελληνικά 1
- Руководство по установке 1
- Русский 1
- Before electric work 2
- Before installation environment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Note the phrase wired remote controller in this installation manual refers only to the par 31maa if you need any information for the other remote controller please refer to either the installation manual or initial setting manual which are included in these boxes 2
- Safety precautions 2
- Ceiling openings and suspension bolt installation locations fig 3 3
- Check the indoor unit accessories fig 3 1 3
- Fig 3 1 3
- Fig 3 3 3
- Installation location 3
- Installing the indoor unit 3
- Refrigerant and drainage piping locations of indoor unit 3
- Branch duct hole and fresh air intake hole fig 3 4 4
- Confirming the position of main unit and tightening the suspension bolts fig 3 8 4
- Fig 3 4 4
- Fig 3 5 4
- Fig 3 6 fig 3 7 4
- Fig 3 8 4
- Installing the indoor unit 4
- Suspension structure give site of suspension strong structure fig 3 5 4
- Unit suspension procedures fig 3 6 4
- Connecting pipes fig 4 1 5
- Fig 4 1 5
- Fig 4 2 5
- Installing the refrigerant piping 5
- Precautions 5
- Drainage piping work 6
- Drainage piping work fig 5 1 6
- Fig 4 3 6
- Fig 5 1 6
- For twin triple combination 6
- Indoor unit fig 4 3 6
- Installing the refrigerant piping 6
- Electrical work 7
- Fig 6 1 7
- Indoor unit fig 6 1 7
- 1 system 8
- Electrical work 8
- On off 1 2 sw8 3 8
- Separate indoor unit outdoor unit power supplies for puhz application only 8
- Simultaneous twin triple quadruple system 8
- Electrical work 9
- Fig 6 3 9
- Fig 6 4 9
- For wired remote controller 9
- For wireless remote controller 9
- Remote controller 9
- Electrical work 10
- Fig 6 5 fig 6 6 10
- Fig 6 7 fig 6 8 10
- Function setting on the unit selecting the unit functions 10
- Function settings 10
- Electrical work 11
- Fig 6 10 11
- Function setting on the remote controller 11
- Electrical work 12
- Explanation of word refrigerant address no and unit no are the numbers given to each air conditioner outlet no is the number given to each outlet of air conditioner refer to the right up down air direction is the direction angle to fix 12
- Fixed setting 12
- How to set the fixed up down air direction only for wired remote controller and puhz pu h application 12
- Only the particular outlet can be fixed to certain direction with the procedures below once fixed only the set outlet is fixed every time air conditioner is turned on other outlets follow up down air direction setting of the remote controller 12
- Remote controller setting 12
- Before test run 13
- Electrical work 13
- Test run 13
- Using wired remote controller 13
- Fig 7 1 14
- Fig 7 3 14
- Fig 7 4 14
- Self check 14
- Test run 14
- Using sw4 in outdoor unit 14
- Test run 15
- Check of drainage fig 7 5 16
- Fig 7 5 16
- System control 16
- Test run 16
- Checking the contents fig 1 17
- Fig 9 4 17
- Installing the grille 17
- Preparations fig 9 5 17
- Preparing to attach the grille fig 17
- Removing the corner panel fig 9 4 17
- Removing the intake grille fig 3 17
- Selection of the air outlets 17
- Fig 9 10 18
- Fig 9 8 18
- Installation of i see sensor corner panel fig 9 10 18
- Installing the grille 18
- Installing the intake grille fig 18
- Securing the grille fig 9 7 18
- Temporary installation of the grille fig 9 6 18
- Wire connection fig 9 8 18
- Easy maintenance function 19
- Fig 11 19
- Installing the grille 19
- Locking the up down airflow direction fig 9 11 19
- Меры предосторожности 00 2 место установки 01 3 установка внутреннего прибора 01 4 прокладка труб хладагента 03 5 дренажные трубы 04 20
- Мерыпредосторожности 20
- Передтестовымпрогоном 20
- Передустановкой окружающаясреда 20
- Передустановкойилиперемещением 20
- Передэлектрическимиработами 20
- Содержание 20
- Электрические работы 05 7 выполнение испытания 211 8 управление системой 14 9 установка вентиляционной решетки 15 10 функция простого техобслуживания 17 20
- Местоустановки 21
- Проверьтеналичиедополнительныхприна длежностейквнутреннемуприбору fig 1 21
- Расположение труб хладагента и дренажных трубдлявнутреннегоблока 21
- Расположениеотверстиявпотолкеинавесных болтов fig 2 21
- Установкавнутреннегоприбора 21
- Fig 6 fig 7 22
- Отверстиедляответвлениявентиляционногоканалаи входноеотверстиедлясвежеговоздуха fig 4 22
- Подвеснаяконструкция обеспечьте прочностьнаместеподвешивания fig 5 22
- Порядокподвешиванияприбора fig 6 22
- Проверка расположения главного прибора и затягиваниенавесныхболтов fig 8 22
- Установкавнутреннегоприбора 22
- Мерыпредосторожности 23
- Прокладкатрубхладагента 23
- Соединениетруб fig 1 23
- Внутреннийприбор fig 3 24
- Длякомбинациииздвух трехэлементов 24
- Дренажныетрубы 24
- Дренажныетрубы fig 1 24
- Прокладкатрубхладагента 24
- Fig 6 1 25
- G g g g 25
- Внутреннийприбор fig 1 25
- Электрическиеработы 25
- On off 1 2 sw8 3 26
- Если у внутреннего и наружного приборов различные источники электропитания см таблицу ниже при использовании комплекта клемм источника электропитания внутреннего прибора замените проводку распределительной коробки внутреннего прибора в соответствии с рисунком справа и измените настройки микропереключателя панели управления наружного прибора 26
- Изменение соединения разъема распределитель ной коробки внутреннего прибора 26
- Комплект клемм источника электропитания внутреннего прибора дополнительно 26
- Настройка микропереключателя наружного прибора только при использовании отдельных источников электропитания для внутреннего прибора наружного прибора 26
- Одновременная двойная тройная четверная система 26
- Система 1 1 26
- Электрическиеработы 26
- Длябеспроводногопультадистанционногоуправления 27
- Дляпроводногопультадистанционногоуправления 27
- Пультдистанционногоуправления 27
- Электрическиеработы 27
- Fig 5 fig 6 28
- Fig 7 fig 8 28
- Установкифункций 28
- Электрическиеработы 28
- Fig 10 29
- Функциональнаянастройканапультедистанционного управления 29
- Электрическиеработы 29
- Порядокнастройкификсированного направленноговниз потокавоздуха толькодляпроводногопультадистанционногоуправле нияидляпримененияpuhz pu h 30
- Пояснениетерминов охладителя и изделия это номера присваиваемые каж дому кондиционеру выпускного отверстия это номер каждого выпускного отверс тия кондиционера см рисунок справа направление воздуха вверх вниз это фиксируемое направление угол 30
- Примечание 0 означает все отверстия 30
- Установка пульта 30
- Фиксация 30
- Электрическиеработы 30
- Выполнениеиспытания 31
- Передпробнымпрогоном 31
- Электрическиеработы 31
- Выполнениеиспытания 32
- Использованиеsw4внаружномблоке 32
- Самодиагностика 32
- Выполнениеиспытания 33
- Выполнениеиспытания 34
- Дозавершенияэлектрическихработ 34
- Послезавершенияэлектрическихработ 34
- Проверкадренажа fig 5 34
- Управлениесистемой 34
- Выборвытяжныхотверстий 35
- Подготовка fig 5 35
- Подготовкакустановкевентиляционнойрешет ки fig 2 35
- Проверкасодержимогокомплекта fig 1 35
- Удалениевоздухозаборнойрешетки fig 3 35
- Удалениеугловойпанели fig 4 35
- Установкавентиляционнойрешетки 35
- Fig 10 36
- Временнаяустановкавентиляционнойрешетки fig 6 36
- Креплениевентиляционнойрешетки fig 7 36
- Примечание неоставляйтеизлишекпроволочноговыводавэлектрической ответвительнойкоробкеприбора 36
- Соединениепроводов fig 8 36
- Установка угловой панели i see sensor fig 10 36
- Установкавентиляционнойрешетки 36
- Установкавоздухозаборнойрешетки fig 9 36
- Fig 11 37
- Блокировканаправлениявоздушногопотока вверх вниз fig 11 37
- Проверка 37
- Установкавентиляционнойрешетки 37
- Функцияпростоготехобслуживания 37
Похожие устройства
- Mitsubishi Electric PLA-ZRP100BA / PUHZ-SHW112VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-ZRP100BA / PUHZ-SHW112VHA Инструкция по установке
- Victoria Arduino Adonis 3 Gr белая Инструкция по эксплуатации
- Victoria Arduino Athena leva 3 Gr латунь 220В Инструкция по эксплуатации
- Victoria Arduino Adonis T3 2 Gr белая Инструкция по эксплуатации
- Victoria Arduino Athena leva 2 Gr латунь 380В Инструкция по эксплуатации
- Victoria Arduino Athena leva 2 Gr медь 220В Инструкция по эксплуатации
- Victoria Arduino Athena leva 2 Gr латунь 220В Инструкция по эксплуатации
- Victoria Arduino Venus Bar 2 Gr S медь Инструкция по эксплуатации
- Smeg SF4120VC Инструкция по эксплуатации
- Victoria Arduino Athena leva 3 Gr медь 220В Инструкция по эксплуатации
- Victoria Arduino Adonis T3 3 Gr белая Инструкция по эксплуатации
- Smeg SF4390VCX Инструкция по эксплуатации
- Victoria Arduino Athena leva 3 Gr латунь 380В Инструкция по эксплуатации
- Victoria Arduino Venus Bar 3 Gr S медь Инструкция по эксплуатации
- Victoria Arduino Venus Family медь Инструкция по эксплуатации
- Bartscher IW 35 со сковородой Инструкция по эксплуатации
- Bartscher IW 35 со сковородой Электрическая схема
- Bartscher IW 35 со сковородой Схема
- Lainox REV101M Инструкция по эксплуатации