Mitsubishi Electric PKFY-P50VHM-E [20/40] Pcfy p vkm e series

Mitsubishi Electric PKFY-P20VBM-E [20/40] Pcfy p vkm e series
20
GB
12. Specifications
PCFY-P·VKM-E Series
Model P40 P63 P100 P125
Power source (Voltage<V>/Frequency) <Hz> ~/N 220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 4.5/5.0 7.1/8.0 11.2/12.5 14.0/16.0
Dimension (Height) <mm> 230
Dimension (Width) <mm> 960 1280 1600
Dimension (Depth) <mm> 680
Net weight <kg> 24 32 36 38
Fan Airflow rate (Low-Middle2-Middle1-High) <m
3
/min> 10-11-12-13 14-15-16-18 21-24-26-28 21-24-27-31
Noise level (Low-Middle2-Middle1-High) <dB> 29-32-34-36 31-33-35-37 36-39-41-43 36-39-42-44
Note
* Operation temperature of indoor unit.
Cooling mode: 15°CWB - 24°CWB
Heating mode: 15°CDB - 27°CDB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19°C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
PKFY-P·VBM-E Series PKFY-P·VHM-E Series
Model P15 P20 P25 P32 P40 P50
Power source (Voltage<V>/Frequency) <Hz> ~/N 220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 1.7/1.9 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3
Dimension (Height) <mm> 295 295
Dimension (Width) <mm> 815 898
Dimension (Depth) <mm> 225 249
Net weight <kg> 10 13
Fan Airflow rate (Low-Middle2-Middle1-High) <m
3
/min>
4.9-5.0-5.2-5.3
4.9-5.2-5.6-5.9 9-10-11 9-10.5-11.5 9-10.5-12
Noise level (Low-Middle2-Middle1-High) <dB> 29-31-32-33 29-31-34-36 34-37-41 34-38-41 34-39-43
Note
* Operation temperature of indoor unit.
Cooling mode: 15°CWB - 24°CWB
Heating mode: 15°CDB - 27°CDB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19°C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
PMFY-P·VBM-E Series
Model P20 P25 P32 P40
Power source (Voltage<V>/Frequency) <Hz> ~/N 220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0
Dimension (Height) <mm> 230 (30)
Dimension (Width) <mm> 854 (1000)
Dimension (Depth) <mm> 395 (470)
Net weight <kg> 14 (3.0)
Fan Airflow rate (Low-Middle2-Middle1-High) <m
3
/min>
6.5-7.2-8.0-8.6
7.3-8.0-8.6-9.3
7.7-8.7-9.7-10.7
Noise level (Low-Middle2-Middle1-High) <dB> 27-30-33-36 32-34-36-37 33-35-37-39
Note
* Operation temperature of indoor unit.
Cooling mode: 15°CWB - 24°CWB
Heating mode: 15°CDB - 27°CDB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
*2 This figure ( ) indicates panel’s.
PFFY-P·VKM-E Series
Model P20 P25 P32 P40
Power source (Voltage<V>/Frequency) <Hz> ~/N 220-230-240/50
Capacity (Cooling/Heating) <kW> 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0
Dimension (Height) <mm> 600
Dimension (Width) <mm> 700
Dimension (Depth) <mm> 200
Net weight <kg> 14
Fan Airflow rate (Low-Middle2-Middle1-High) <m
3
/min>
5.9-6.8-7.6-8.7
6.1-7.0-8.0-9.1
8.0-9.0-9.5-10.7
Noise level (Low-Middle2-Middle1-High) <dB> 27-31-34-37 28-32-35-38 35-38-42-44
Note
* Operation temperature of indoor unit.
Cooling mode: 15°CWB - 24°CWB
Heating mode: 15°CDB - 27°CDB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB

Содержание