Toshiba MMC-AP0184H-E — инструкция по демонтажу и установке вентилятора и дренажного поддона [128/219]

Toshiba MMC-AP0184H-E [128/219] No part name procedure remarks
127
7
Fan motor
1. Detachment
1) Perform works 1. of 2, 1. of 3, 1. of 6.
2) Remove lead wires which are connected to the following
connectors of P.C. board assembly.
NOTE
Unlock locks of the housing, and then remove the connectors.
CN333: Fan motor power supply (5P: White)
CN334: Detection of fan motor (5P: White)
Remove tie wrap which fixes lead wires.
3) Remove the noise filter from lead wire to detect fan motor
position.
4) Take off screws of fan motor fixing bracket.
Earth wires of the motor are tightened together.
(Ø5 × 10, 2 pcs)
Remove tie wrap which fixes the lead wires.
5) Remove fixing bracket of the fan motor by holding it with
hands so that the fan motor does not fall down.
2. Attachment
1) Mount the fan motor as before in order, Fan motor Fixing
bracket of fan motor Noise filter Lead wire process
E-cover.
NOTE
Check there is no missing or poor contact of the connectors.
Check also that the multi blade fan turns surely and smoothly, and check togethertightening of motor earth.
8
Under panel Drain
pan assembly
1. Detachment
1) Take off the drain cap and drain the drain water
accumulated in the drain pan assembly.
In case of natural drain model, drain the drain water by
taking off hose band and drain hose.
NOTE
When taking off drain cap and drain hose, be sure receive drain
water in a bucket, etc.
2) Take off screws fixing the under panel while holding it to
remove. (Ø4 × 10, 8 pcs)
NOTE
Be careful that sheeting metal does not fall when removing the
under panel.
3) Pull out the drain pan assy. by holding handle at lower part.
NOTE
When pulling out the drain pan assy., never pull out the drain
socket by drawing it with hands. If doing so, water leak may be
caused.
4) Pull out it to some extent, lay hand on the bump at suction
side, and then remove the drain pan assembly.
2. Attachment
1) Hook and attach the drain pan assy. to the flange at
discharge side, and then push in.
2) Using screws taken off in procedure 1. 2) of 8, attach under
panel by holding with hands.
3) Attach drain cap, hose band, and drain hose as before,
which were taken off in procedure 1. 1) of 8.
NOTE
Finally, be sure to check there is no water leakage from each
attached part.
No. Part name Procedure Remarks
Noise filter
Earth lead
Drain cap or drain hose
Never hold and pull
the drain socket.
Under panel
Drain pan assembly