Toshiba MMC-AP0184H-E [30/219] Refrigerant cycle diagram

Toshiba MMC-AP0244H-E [30/219] Refrigerant cycle diagram
29
3 Refrigerant Cycle Diagram
Indoor unit
CAUTION
MMU-AP0074YH, AP0094YH, AP0124YH type air conditioners have no TC2 sensor.
Explanation of functional parts in indoor unit
Functional part name Functional outline
Pulse Motor Valve
PMV
(Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls under cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
Temp. Sensor
1.TA
(Connector CN104 (2P): Yellow)
1) Detects indoor suction temperature
2.TC1
(Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
3.TC2
(Connector CN101 (2P): Black)
1) Controls PMV under cool in heating operation
4.TCJ
(Connector CN102 (2P): Red)
1) Controls PMV super heat in cooling operation
2) [MMU-AP0074YH to AP0124YH only] Controls PMV under cool in heating operation
Capillary tube
Gas side
Heat exchanger at
indoor side
Pulse Motor
Valve (PMV)
Sensor
(TC2)
Liquid
side
Strainer
Sensor
(TCJ)
Sensor
(TA)
Fan
Fan motor
Sensor
(TC1)