MCZ Forma B95 [10/46] Examples of flue pipes
![MCZ Forma 115 [10/46] Examples of flue pipes](/views2/1336204/page10/bga.png)
INSTALLATION AND USE MANUAL
Chapter 2
page 10
Theoretical notions for installation
Technical service – MCZ S.p.A. all rights reserved - Reproduction prohibited
2.5.1. Examples of flue pipes
Square or rectangular section flue pipes must have rounded internal
corners with radius not less than 20mm. For the rectangular section,
the ratio between internal dimensions must be ≤1.5.
The sections/lengths of the flue pipe shown in the technical data table
are guidelines for correct installation. Any alternative configurations
must be suitably sized in accordance with EN13384-1.
The smoke duct should be equipped with a solid material collection
chamber at the mouth of the smoke duct to be easily opened with an
airtight door.
IMPORTANT !
In the event of doubt on your chimney flue operations or
that its dimensions are different from those recommended,
we highly suggest an authorised MCZ technician inspect and
measure chimney flue performance (micro-gauge
measurements)
MCZ s.p.a. shall not be held liable for poor operation of the
fireplace stove that is due to a flue pipe of improper size or
installation that does not comply with provided
requirements.
AISI 316 stainless steel
flue pipe with dual
chamber insulated with
ceramic wool or equivalent
resistant to 400°C.
EXCELLENT
Flue pipe in refractory brick
with insulated double wall and
external coat of cement mix
lightened with honeycomb
material such as clay.
GOOD
Traditional square section
clay flue pipe with insulating
hollow inserts.
GOOD
Avoid flue pipes with internal
rectangular sections whose
larger side is double the smaller
such as 20x40 or 15x30.
AVERAGE
Содержание
- Use and installation manual 1
- Contents 2
- Contents 3
- How to read the manual 4
- Introduction 4
- Manual preservation 4
- Revisions to the publication 4
- These symbols signal specific messages in this booklet 4
- Operating warnings 5
- Safety warnings 5
- Warnings and warranty conditions 5
- Exclusions 6
- Important information for correct disposal of the product in accordance with ec directive 2002 96 ec 6
- Restrictions 6
- Warranty conditions 6
- Installation in accordance with uni 10683 7
- Operating area 7
- Precautions 7
- Connection to the external air intake 8
- Important 8
- Connection to the flue pipe 9
- Flue pipe 9
- Examples of flue pipes 10
- Important 10
- Technical specifications 17
- Installation and assembly 20
- Preparation and unpacking 20
- Selection of operating mode 20
- Forced convection vf 21
- Natural convection vn 21
- Positioning 21
- Release of counterweights 21
- Adjustment of height and balancing 22
- Air inlet for forced ventilation 23
- Air inlet for natural ventilation 23
- Combustion air inlet 23
- Ducts for kit comfort air 23
- External and internal air intake 23
- Connection to the flue pipe 24
- Installation of cladding and hood 24
- Hood ventilation nozzles 25
- Insulating a wooden beam 25
- Insulation of fireplace stove 25
- Comfort air kit natural ventilation and forced 26
- Components of forced ventilation kit with and without illumination 26
- Components of natural ventilation kit with and without illumination 26
- Ventilation 26
- A c d b 27
- Installation of the comfort air kit 29
- Variation for air outlet with container 30
- Variation for air outlet with illumination 30
- Maintenance of air outlet with illumination 31
- Composition of control unit 32
- Control unit 32
- Positioning of the control unit 32
- General information on the control unit 33
- On off 33
- Operation 33
- Light on if present 34
- Replacing the fuse of the control unit 34
- Safety function 34
- Door open switch 35
- Installation of temperature probe 35
- Connections 36
- Replacing the fan 37
- Attention 38
- Do not demand full heating 38
- Operating test 38
- Operation 38
- Performance straight away 38
- Pre lighting warnings 38
- Choice of fuel 39
- Phases for first test lighting 39
- First lighting 40
- Attention 41
- Loading the fuel 41
- Control of combustion 42
- Emergency situations 42
- Cleaning out the ashes 43
- Cleaning the glass 43
- Cleaning the refractory material walls alute 43
- Cleaning to be performed by the user 43
- Maintenance and cleaning 43
- Electric fan 44
- Lubrication and routine maintenance of the extensible guides 44
- Maintenance of kit vf if installed 44
- Cleaning flue pipe 45
- Cleaning to be dealt with by specialized technician 45
- Control unit comfort air 45
- Wiring 45
- E mail mcz mcz it 46
- Fax 39 0434 599598 46
- Internet www mcz it 46
- Mcz group s p a 46
- Telephone 39 0434 599599 pbx 46
- Via la croce n 8 46
- Vigonovo di fontanafredda pn italy 46
Похожие устройства
- MCZ Forma B95 Сертификат
- MCZ Forma 95 dx Инструкция по эксплуатации
- MCZ Forma 95 dx Сертификат
- MCZ Forma 65 Инструкция по эксплуатации
- MCZ Forma 65 Сертификат
- MCZ Forma 115 Инструкция по эксплуатации
- MCZ Forma 115 Сертификат
- MCZ Forma 95 sx Инструкция по эксплуатации
- MCZ Forma 95 sx Сертификат
- MCZ Forma 95 Инструкция по эксплуатации
- MCZ Forma 95 Сертификат
- MCZ Forma 75 sx Инструкция по эксплуатации
- MCZ Forma 75 sx Сертификат
- MCZ Forma 75 dx Инструкция по эксплуатации
- MCZ Forma 75 dx Сертификат
- MCZ Forma T95 Инструкция по эксплуатации
- MCZ Forma T95 Сертификат
- MCZ Forma 75 Инструкция по эксплуатации
- MCZ Forma 75 Сертификат
- MCZ Forma T50 Инструкция по эксплуатации