3 - Description
3.1 - Inspection and storage
When the equipment is received, all items must be carefully
checked against the bill of lading to be sure all crates and
cartons have been received. The units are shipped on pallet.
Inspect all units for visible or concealed damages.
In case of deterioration, formulate the precise reserves
on the transport document and send immediately a
registered letter to the forwarder, mentioning clearly
the occured damages and a copy of the letter to the
manufacturer or its representative.
3.2 - Electrical Data
3.3 - Operating Limits
Do not stand or transport the unit on its end. Temporary
storage must be indoor, completely sheltered from rain,
snow, etc.
Change in the weather (high and low temperatures) should
not damage the unit. Excessively high temperature (60 °C or
more) may deteriorate certain plastic materials and cause
permanent damages.
In addition, some electric components and solid-state circuit
boards may not operate correctly.
MODELS 1.39 2.69 3.99
Low speed
A 1.40 2.02 3.30
Medium speed A 2.40 3.00 3.95
High speed A 3.30 4.22 5.01
Motor absorbed current - 230 V / 1 ph / 50 Hz
Electric heaters - 400 V / 3 ph / 50 Hz
MODELS 1.39 2.69 3.99
Coils BE1 BE2 BE3 * BE1 BE2 BE3 * BE1 BE2 BE3 *
Capacity (kW) 3 6 9 6 12 18 12 24 36
Voltage
400 V / 3 / 50 Hz – (230 V / 3 / 50 Hz : optional)
Number of stages 1 2 3 1 2 3 1 2 3
WATER PIPING SYSTEM
Maximum operating pressure 10 bars
Minimum entering temperature + 4 °C
Maximum entering temperature + 90 °C
ROOM AIR TEMPERATURE
Minimum temperature 5 °C
Maximum temperature 32 °C
SUPPLY VOLTAGE
230 V ± 10 % / 1 ph / 50 Hz
(*) BE3 is to be used on fan discharge only.