Airwell SLH 1902 [6/40] Operating limits

Airwell SLH 3804 [6/40] Operating limits
Page 6
Operating Limits
Notes :
1) Flow rate and pressure drop given for SLH BLN units. On models
2804 to 3804, the flow rate and pressure drop are given for
each evaporator.
2) Minimum ambient temperature : -18 °C with fan speed
controller (optional).
Notes :
1) Flow rate and pressure drop given for SLH BLN units.
2) Minimum ambient temperature : -18 °C with fan speed
controller (optional).
3) Data given for water volume of 7.5 litres/kW.
4) Tolerance : 400 V ± 10 %.
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
Water outlet °C
Brine outlet (low liquid
temperature application)
°C
Water temp. difference K
Flow rate (1) l/s
7.8 20.8 8.7 23.3 9.8 26.0 10.6 28.2 12.0 31.9 12.6 33.5 13.6 36.3
Pressure drop (1) kPa 11.7 83.1 14.7 104.6 12.5 89.2 11.0 78.0 14.0 99.9 15.5 109.9 13.4 95.6
Maximum operating pressure - Water side bar
Cooling - BLN version °C
Cooling - LN version °C
Cooling - ELN version °C
Cooling - HET version °C
Heating °C
Standard fans Pa
High pressure fans Pa
Liquid outlet temperature °C
Maximum operating pressure - Water side bar
litres
Nominal supply voltage (4) V 400 V / 3 Ph / 50 Hz
Hot
water
+30 °C to +50 °C
10
Recommended minimum water volume of the system
(water tank + installation) (3)
1956 3008 34202658 3155
SLH models
1202
Ambient
air
Air entering
temperature
-5 °C (2) to +44 °C
-18 °C to +40 °C
-5 °C(2) to +46 °C
-5 °C to +20 °C
External static
pressure
80
Chilled
liquid
Liquid outlet
temperature
+5 to +15
Not available
3 to 8
10
2194 2450
22021802 2002
0
-18 °C to +44 °C
1402 1602 1902
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
Water outlet °C
Brine outlet (low liquid
temperature application)
°C
Water temp. difference K
Flow rate (1) l/s 14.2 37.8 15.8 42.1 8.7 23.3 9.8 26.0 10.6 28.2 11.6 30.9
Pressure drop (1) kPa 14.6 103.7 16.0 114.1 14.7 104.6 12.5 89.2 11.0 78.0 13.1 93.3
Maximum operating pressure - Water side bar
Cooling - BLN version °C
Cooling - LN version °C
Cooling - ELN version °C
Cooling - HET version °C
Heating °C
Standard fans Pa
High pressure fans Pa
Liquid outlet temperature °C
Maximum operating pressure - Water side bar
litres
Nominal supply voltage (4) V
Ambient
air
Air entering
temperature
External static
pressure
3204
Chilled
liquid
Liquid outlet
temperature
SLH models
26022402
Not available
Hot
water
Recommended minimum water volume of the system
(water tank + installation) (3)
3962 4387
+30 °C to +50 °C
10
3 to 8
+5 to +15
36042804 3804
10
-5 °C (2) to +44 °C
-18 °C to +44 °C
-18 °C to +40 °C
400 V / 3 Ph / 50 Hz
-5 °C(2) to +46 °C
-5 °C to +20 °C
0
80
4901 58133562 5316
3) Data given for water volume of 7.5 litres/kW.
4) Tolerance : 400 V ± 10 %.