8. Summary of faults
Before removing the terminal box cover and before
any dismantling of the pump, do not fail to switch
off the entire power supply.
Fault Cause Remedy
Pump does not run Pump blocked deblock, see section 6.4
No voltage in motor check switch and fuses
check power supply
Voltage too low check control and mains
Short circuit Motor incorrectly
when pump switched o connected connect correctly
Motor defective replace pump
Pump emits noises Air in the pump deaerate system and pump,
see section 6
Cavitation increase system pressure/
reduce temperature
Pump too powerful smaller electric setting/
smaller pump
Power setting Check power setting of pump
Radiators do not warm up Pump too weak install more powerful pump
Air in the pump deaerate system and pump,
see section 6
Subject to technical alterations
english
25
Before commencing maintenance works, do not fail
to put the pump out of action, pull all pins out of
the power supply and secure it against becoming
switched on again. Implementation only by specialist
staff.
Observe operating instructions.
Only carry out the works with the plant at a standstill.
Disconnect pump from power supply.
Switch off fuse and mount warning board.
Risk of scalding from emerging medium.
Risk of burning from hot surfaces.