Ecoflam MULTICALOR 100 PR-AB TL VCS 240 [14/64] Ad justem en t o f th e co m bustio n air

Ecoflam MULTICALOR 100 PR-AB TL VCS 350 [14/64] Ad justem en t o f th e co m bustio n air
14
420010239601 Multicalor 45 ÷ 140 PR/PR
EN
AD JU STEM EN T OF TH E COM BUSTION AIR
Remove cover to gain access to the adjusting cams.The cams are to be adjusted
through the suitable key provided for. Description:
I-Limit switch for air damper “High Flame” position adjustment
(Max. power)
II - Limit switch for the air damper position at burner’s shut down
III - Limit switch for air damper “Low Flame” position adjustment
(Min. power)
V - Limit switch "NOT USED".
LAN D IS & STA EFA SQ N 30/31 251A 2700 AIR DAM PER MOTOR
MANUAL RELEASE
SWITCH
2
SELECTOR
0
AUTO
0 =
operating elements locked
in an intermediate position
=
operation on maximum capacity
=
operation on minimum capacity
AUTO =
automatic operation
1
3
AIR AD JUSTM EN T
A D JU S T IN G TH E MAXIMUM CAPACITY OF TH E BU RN ER
Position the selector, situated on the control panel, on position maximum power and proceed as follows:
Adjusting the maximum gas flow rate: - proceed as stated in the regulating the solenoid valves until you achieve the
correct gas flow, as established by analyzing the combustion process. Eventually adjust the gas flow rate using a suitable
allen wrench, alter the position of the cam(3) guide blade; if you screw it down, the flow rate is reduced; if you unscrew
it, the flow rate increases.
Adjusting the maximum air flow rate:Eventually adjust this position acting on the screw “1 “, after loosening nut “ 2
“.
Tighten the nut “2” in place once again.
A D JU S T IN G TH E MINIMUM CAPACITY OF TH E BU RN ER
Position the selector, situated on the control panel, on position minimum power and proceed as follows:
Adjusting the minimum gas flow rate: using a suitable Allen wrench, alter the position of the cam(3) guide blade; if
you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
Adjusting the minimum air flow rate: adjust on limit switch for air damper “Low Flame” position adjustment.
A D JU S T IN G TH E IN T E R M E D IA T E BU RN ER CAPACITIES
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjusting the intermediate gas flow rates:using a suitable Allen wrench, alter the position of the cam(3) guide blade; if
you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.