Ecoflam MULTICALOR 100 PR-AB TL VCS 240 [16/64] Ligh t o il circuit

Ecoflam MULTICALOR 70 PR-AB TL MB-DLE 410 [16/64] Ligh t o il circuit
16
420010239601 Multicalor 45 ÷ 140 PR/PR
EN
The correct length of pipes is calculated by summing up the length of all vertical and horizontal right sections and
bends. The static suction head will be the distance between the non-return valve and the burner’s pump axle.
The depression must not be greater than 0.45 bar; should it be higher, some damage could occur to the pump, with
consequent increase in mechanical noises and ,eventually, a failure.
MAXIMUM LEN G TH OF SU C T IO N LIN ES FO R TW O-PIPE SYST EM
H
(m)
ø 10 mm ø 12 mm
0
0,5
1
2
3
3,5
32
36
40
48
56
60
90
90
90
90
90
90
ø 14 mm ø 16 mm
22
25
30
35
38
40
38
45
50
60
70
80
AS 67 / AN 77
(m)
AJ 6
(m)
H
H
H
(m)
ø 10 mm ø 12 mm
0
0,5
1
2
3
3,5
25
21
18
10
5
---
70
62
54
38
20
10
ø 14 mm ø 16 mm
25
20
18
10
5
2
45
38
33
20
10
4
AS 67 / AN 77
(m)
AJ 6
(m)
Two-pipe lift system
Two-pipe siphon feed system
Pipe length
Pipe length
2
3
5
87
6
VgR
Vg
A
R
VgS
VG
VGS
1
4
LIG H T-OIL CIRCUIT
A - HOSE
B - OIL FILTER
C - OIL COCK
1 - PUMP
2 - SAFETY OIL VALVE
3 - OIL VALVE
4 - RETURN OIL VALVE
5 - NOZZLE
6- GAS PRESSURE SWITCH
7- SAFETY GAS VALVE
8- GAS VALVE