Danfoss VLT Refrigeration Drive FC103 FC-103P11KT2 [140/203] Refrigeration drive programming guide

Danfoss VLT Refrigeration Drive FC-103N160 [140/203] Refrigeration drive programming guide
22-84 Speed at No-Flow [Hz]
Range: Function:
Size
related*
[ 0 - par.
22-86
Hz]
Resolution 0.033 Hz.
The speed of the motor at which flow has
effectively stopped and minimum
pressure H
MIN
is achieved should be
entered here in Hz. Alternatively, the
speed in RPM can be entered in
22-83 Speed at No-Flow [RPM]. If it has
been decided to use Hz in 0-02 Motor
Speed Unit then 22-86 Speed at Design
Point [Hz] should also be used. Closing
the valves and reducing the speed until
minimum pressure H
MIN
is achieved will
determine this value.
22-85 Speed at Design Point [RPM]
Range: Function:
Size
related*
[ par.
22-83
-
60000
RPM]
Resolution 1 RPM.
Only visible when 22-82 Work Point
Calculation is set to Disable. The speed
of the motor at which the System
Design Working Point is achieved should
be entered here in RPM. Alternatively,
the speed in Hz can be entered in
22-86 Speed at Design Point [Hz]. If it has
been decided to use RPM in 0-02 Motor
Speed Unit then 22-83 Speed at No-Flow
[RPM] should also be used.
22-86 Speed at Design Point [Hz]
Range: Function:
Size
related*
[ par.
22-84
-
par. 4-19
Hz]
Resolution 0.033 Hz.
Only visible when 22-82 Work Point
Calculation is set to Disable. The speed of
the motor at which the System Design
Working Point is achieved should be
entered here in Hz. Alternatively, the
speed in RPM can be entered in
22-85 Speed at Design Point [RPM]. If it
has been decided to use Hz in
0-02 Motor Speed Unit, then 22-83 Speed
at No-Flow [RPM] should also be used.
22-87 Pressure at No-Flow Speed
Range: Function:
0 * [ 0 - par. 22-88 ] Enter the pressure H
MIN
corresponding
to
Speed at No Flow in Reference/Feedback
Units.
Also see 22-82
Work Point Calculation point D.
22-88 Pressure at Rated Speed
Range: Function:
999999 * [ par.
22-87
-
999999.999 ]
Enter the value corresponding to
the Pressure at Rated Speed, in
Reference/Feedback Units. This
value can be defined using the
pump datasheet.
Also see 22-82
Work Point Calculation point A.
22-89 Flow at Design Point
Range: Function:
0 * [0 - 999999.999 ] Enter the value corresponding to the
Flow
at Design Point. No units necessary.
Also see 22-82
Work Point Calculation point C.
22-90 Flow at Rated Speed
Range: Function:
0 * [0 - 999999.999 ] Enter the value corresponding to Flow at
Rated
Speed. This value can be defined
using the pump datasheet.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
139
3 3