Danfoss FCM 307 [15/106] Fcm series

Danfoss FCM 307 [15/106] Fcm series
X101: Terminal block for analogue/digital control signals
Terminal No.
Function Example
1 Analogue input (0-20 mA) Feedback signal
2 Analogue (0-10 V)/digital input 2 Speed reference
3 Digital input (or pulse) 3 Reset
4 Digital input (or precise stop) 4 Start
5 Digital input (other) 5 Jog (fixed speed)
6 24 V DC supply for digital inputs (max. 150 mA)
7 10 V DC supply for potentiometer (max. 15 mA)
8 0 V for terminals 1-7 and 9
9 Analogue (0-20 mA)/digital output Fault indication
Connection diagram - factory setting
-
Reset to be closed short time for resetting fault trips
- Start to be closed for changing to run mode
- Jog will run at fixed speed while closed (10 Hz)
- Speed reference (0-10 V) determines speed while in
run mode
X102: Terminal block for relay output
Terminal No. Function
1-2 Make (normally open)
1-3 Brake (normally closed)
See parameter 323 (relay output) for programming of
relay output.
X100: Terminal block for data communication
Terminal No.
Function
1 P RS 485 for connection to
bus or PC
2 N RS 485
3 5 V DC Supply for RS
485 bus
4 0 V DC
LED 300-304
LED 300 (red): Fault trip
LED 301 (yellow): Warning
LED 302 (green): Power on
LED 303-304: Communication
For PROFIBUS versions please refer to the manual
MG.90.AX.YY.
VLT
®
FCM Series
MG.03.H6.02 - VLT
®
is a registered Danfoss trademark 15