15 SUMMARY TABLE OF WEIGHTS
This drawing illustrates the points of the machine for which the weights for the basic chiller and heat
pump models have been calculated. The values are shown in the following tables.
Important note:
the weights of hydronic modules (C-H; with 2 pumps + tank, with 1 pump +
reservoir, with 2 pumps, with 1 pump) must be added to the standard weights of the basic model
(C-H; STD cooling-only, STD heat pump, Free-Cooling STD).
NOTE: all weights indicated above include the refrigerant charge and water contained in the hydraulic
system (very important for determining the most suitable support for the unit, especially if equipped with a
tank).
To obtain the approximate weight of the unit when empty, subtract the weight in kg of the water contained
in the tank – see table below. In other cases the water content is negligible for these purposes.
FRAME LENGTH DEPTH HEIGHT
H2O in the
buffer tank
[Kg]
Rubber anti-
vibration
device
Spring anti-vibration
device
1
2090 1183 1735 200 DD10040M-M16 ISOTOP SD7-M10
2
2440 1183 1735 220 DD10040M-M16 ISOTOP SD7-M10
3
3190 1183 1735 340 DD10040M-M16 ISOTOP SD7-M10
3+
3540 1183 1735 340 DD10040M-M16 ISOTOP SD7-M10
4
3540 1653 1823 600 DD10040M-M16 ISOTOP SD7-M10
5
3540 1653 2223 600 DD10040M-M16 ISOTOP SD7-M10
6
4206 1653 2330 765 60017033-M20 ISOTOP SD8-M10