Galletti LCE 364 HS [7/64] Configurations

Galletti LCE 364 HS [7/64] Configurations
LCE
RG66004766_rev.05
7
Below is a list of all possible models, broken down by efficiency pack :
efficiency pack 1 efficiency pack 2 efficiency pack 4
Indicative cooling
capacity of the
“cooling-only”
version [kW]
- LCE042CL/CQ - 48
- LCE042HL/HQ - 48
- LCE052CL/CQ - 53
- LCE052HL/HQ - 53
- LCE062CS/CL/CQ - 63
- LCE062HS/HL/HQ - 63
- LCE072CS/CL/CQ - 70
- LCE072HS/HL/HQ - 70
- LCE082CS/CL/CQ - 77
- LCE082HS/HL/HQ - 77
LCE091CS/CL/CQ LCE092CS/CL/CQ LCE094CL/CQ 92
LCE091HS/HL/HQ LCE092HS/HL/HQ LCE094HL/HQ 92
LCE101CS/CL/CQ LCE102CS/CL/CQ LCE104CL/CQ 103
LCE101HS/HL/HQ LCE102HS/HL/HQ LCE104HL/HQ 103
LCE121CS/CL/CQ LCE122CS/CL/CQ LCE124CS/CL/CQ 125
LCE121HS/HL/HQ LCE122HS/HL/HQ LCE124HS/HL/HQ 125
LCE141CS/CL/CQ LCE142CS/CL/CQ LCE144CS/CL/CQ 138
LCE141HS/HL/HQ LCE142HS/HL/HQ LCE144HS/HL/HQ 138
LCE161CS/CL/CQ LCE162CS/CL/CQ LCE164CS/CL/CQ 155
LCE161HS/HL/HQ LCE162HS/HL/HQ LCE164HS/HL/HQ 155
- - LCE174CS 162
- - LCE174HS 162
- - LCE194CS/CL/CQ 187
- - LCE194HS/HL/HQ 187
- - LCE214CS/CL/CQ 209
- - LCE214HS/HL/HQ 209
- - LCE244CS/CL/CQ 237
- - LCE244HS/HL/HQ 237
- - LCE274CS/CL/CQ 271
- - LCE274HS/HL/HQ 271
- - LCE294CS/CL/CQ 296
- - LCE294HS/HL/HQ 296
- - LCE324CS/CL/CQ 314
- - LCE324HS/HL/HQ 314
- - LCE364CS/CL 355
- - LCE364HS 355
FREE-COOLING
Fluid chillers with Free-Cooling exchange designed to cool water or mixtures of water and an antifreeze
agent, intended for civil air-conditioning and industrial cooling systems. LCE chillers, available in versions
with different acoustic designs (“S”, “L”) and cooling circuit architectures (Efficiency pack 1, 4), they cover
a range of cooling capacities from 44 to 355 kW, calculated with reference to standard test conditions of
water 12°/7° - air entering the finned block heat exchangers 35°C and Free-Cooling operating conditions
with an air temperature of +5°C and a temperature differential of the finned block heat exchangers of
15°/12°C.
Configurations: Chiller Free-Cooling F
Versions: Standard version S
Low-noise version – for a low-noise impact L
Efficiency Packs: Efficiency pack 1 1 compressor per circuit
Efficiency pack 4 2 tandem compressors on 2 circuits

Содержание

Скачать