Fuji Electric FRN355VG1S-4J [1002/1046] If the light alarm indication l al appears on the led monitor

Fuji Electric FRN280VG1S-4J [1002/1046] If the light alarm indication l al appears on the led monitor
13-26
13.4 If the "Light Alarm" Indication (l-al) Appears on the
LED Monitor
If the inverter detects a minor abnormal state "light alarm," it can continue the current operation without
tripping while displaying the "light alarm" indication
l-al
on the LED monitor. In addition to the
indication
l-al
, the inverter blinks the KEYPAD CONTROL LED and outputs the "light alarm" signal
L-ALM to a general-purpose digital output terminal to alert the peripheral equipment to the occurrence of a
light alarm. (To use the L-ALM, it is necessary to assign the signal to any of the digital output terminals by
setting any of function codes E15 through E19 to "57.")
Function codes H106 through H110 specify which alarms should be categorized as "light alarm." The
available "light alarm" codes are check-marked in the "Light alarm" object column in Table 13.1.
For the "light alarm" factors and the alarm removal procedure, refer to Chapter 3, Section 3.4.3.5
"Monitoring light alarms."

Содержание

Скачать