Fuji Electric FRN355VG1S-4J [1033/1046] 2 calculation of harmonic current usually calculate the harmonic current according to the sub table 3 three phase bridge rectifier with the smoothing capacitor...

Fuji Electric FRN200SVG1S-4J [1033/1046] 2 calculation of harmonic current usually calculate the harmonic current according to the sub table 3 three phase bridge rectifier with the smoothing capacitor in table 2 of the guideline s appendix table b lists the contents of the sub table 3
App. B
Japanese Guideline for Suppressing Harmonics for Customers Receiving High Voltage or Special High Voltage
A-15
App.
Table B.4 "Input Fundamental Currents" of General-purpose Inverters
Determined by the Applicable Motor Ratings
Applicable motor
rating (kW)
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
200 V 1.62 2.74 5.50 7.92 13.0 19.1 25.6 36.9 49.8 61.4
Input
fundamental
current (A)
400 V 0.81 1.37 2.75 3.96 6.50 9.55 12.8 18.5 24.9 30.7
6.6 kV converted
value (mA)
49 83 167 240 394 579 776 1121 1509 1860
Applicable motor
rating (kW)
22 30 37 45 55 75 90 110 132 160
200 V 73.1 98.0 121 147 180 245 293 357
Input
fundamental
current (A)
400 V 36.6 49.0 60.4 73.5 89.9 123 147 179 216 258
6.6 kV converted
value (mA)
2220 2970 73.5 4450 5450 7450 8910
10850 13090 15640
Applicable motor
rating (kW)
200 220 250 280 315 355 400 450 500 630
200 V
Input
fundamental
current (A)
400 V 323 355 403 450 506 571 643 723 804 1013
6.6 kV converted
value (mA)
19580 21500 24400 27300 30700 34600 39000 43800 48700 61400
(2) Calculation of harmonic current
Usually, calculate the harmonic current according to the Sub-table 3 "Three-phase bridge rectifier
with the smoothing capacitor" in Table 2 of the Guideline's Appendix. Table B.5 lists the contents of
the Sub-table 3.
Table B.5 Generated Harmonic Current (%), 3-phase Bridge Rectifier (Capacitor Smoothing)
Degree 5th 7th 11th 13th 17th 19th 23rd 25th
w/o a reactor 65 41 8.5 7.7 4.3 3.1 2.6 1.8
w/- a reactor (ACR) 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3
w/- a reactor (DCR) 30 13 8.4 5.0 4.7 3.2 3.0 2.2
w/- reactors (ACR and DCR) 28 9.1 7.2 4.1 3.2 2.4 1.6 1.4
- ACR: 3%
- DCR: Accumulated energy equal to 0.08 to 0.15 ms (100% load conversion)
- Smoothing capacitor: Accumulated energy equal to 15 to 30 ms (100% load conversion)
- Load: 100%
Calculate the harmonic current of each degree using the following equation:
100
(%)current harmonicnth Generated
(A)current lFundamenta(A)current harmonicnth ×=