1.3.3 De-superheater for partial heat recovery (optional)
The option ofpartialheat recovery is im
plemented with a brazewelded plateheat exchangerplaced in series on the
finnedpackcondenseranditssizelimitspressuredropsontherefrigerantsidetoaminimum.
Allmachinesconfiguredwithheatrecoveryuseasperstandardmodulatingcondensationcontrol.Topreventalackof
balance in the cooling cir
cuit, if the water temperature is too low when the recovery starts, the hydraulic recovery
circuitisimplementedasindicatedinthefollowingfigure:alowwatertemperatureatrecoverywouldcauseadropin
thecondensationtemperatureandthereforeaninsufficientpressurejumpontheexpansionvalvewiththeensuingrisk
ofthesafetydevic
esbeingtriggered.

The bulb of the 3way mixer valve is placed at the desuperheater exchanger inlet, which by mixing the hot water
produced with colder water from the tank allows you to limit the time needed for the system to reach full operating
capacity to a few moments. A buffer tank must be pla
ced between the unit and the utility since the demand for hot
wateranditsavailabilityarenotsimultaneous,becauseitneedsthecompressorstoberunning.
Itshouldbepointedoutthattheheatrecoveryoutputislinkedtothedispensedcoolingoutputandthat,therefore,in
partialloadsituationsitisalsoreduce
djustthesame;thisaspectmustbetakenintoconsiderationforthedimensions
of the buffer tank. The partial heat recovery option is supplied only with the desuperheater exchanger. The other
componentsofthecircuitlaidoutinthepreviousfigurearenotin
cludedinthesupply.
1.3.4 Utility and dissipation side cycle inversion valves (optional)
WhenLEWHreversiblechillersswitchfromchillertoheatpump,andviceversa,theyperformtwocycleinversions:one
onthecoolantcircuitandoneonthewatercircuit.TheinversionvalveofthewatersidecycleswitchesfrompositionA
to position B and vice versa by means of an electrical driver without cha
nging the direction of travel for the outside
utilities. This allows you to invert the direction of the flow in the heat exchangers, keeping them against the flow in
relationtotherefrigerantfluidineveryoperatingmode.Thewatersidecy
cleinversionvalveisanoptionalcomponent.
TANK
DIVERTER
RECIRCULA
T