KSB Riotec 30-70 [19/19] In the event of high temperatures and high system pressure the pumps should be allowed to cool down danger of liquid boiling over

KSB Riotec 40-100 [19/19] In the event of high temperatures and high system pressure the pumps should be allowed to cool down danger of liquid boiling over
27
Riotec / Riotec Z
Code Fault/error Error- Manual Switch off Cause Solutions
No. LED *) Reset at x
errors/
24 hrs
E52 Communication error O W** IF-modules not plugged in After 5 minutes the modules
master/slave properly, cable defect switch over to single pump mode.
Creel modules again,
Check cable
MA Master/slave not set O W Set master and slave
Pump makes noises O Cavitation as a result of insufficient Increase system-admission
admission pressure pressure (remaining within the
permissible range)
Check pump lift settings, reduce
pump lift if necessary
*) P Permanent light, O LED is off
**) Pump moves from regulator mode to fixed characteristic (depends on the fixed set value, see Fig. 8).
W only a Warning – not error removal (can appear an infinite number of times)
In the event of high temperatures and high
system pressure, the pumps should be
allowed to cool down.
Danger of liquid boiling over!
If the fault cannot be remedied, please contact
your local plumbing and heating specialist or KSB
customer services.
Subject to technical alterations!