High Performance Vector Control/Torque Control Inverter User Manual
150
Appendix C FAQ
A: (2) Check if the control lines for the G-4018/P-4022 or current sensor of above power class are loose
or dislocated.
V. Why was the operating frequency of the inverter kept at 0Hz upon reverse operation?
A: (1) Check if the frequency is set as 0;
A: (2) Check if the inverter function code parameter P3.09 is set as 0. If not, change it to 0.
VI. The inverter had been connected with braking resistor featuring dynamic braking, why didn’t it
work?
A: (1) Check if the braking resistor is connected between the main circuit terminals B1 and B2;
A: (2) Check if the inverter function code parameter PA.09 is set as 1. If not, change it to 1.
VII. Why was there large deviation on the correspondence relation between the analog input and the
setting frequency?
A: (1) Check if the jumpers of analog input type and control board are properly set. For the analog voltage
input, toggle the corresponding channel to the V end of the jumper; for the analog current input, toggle the
corresponding channel to the I end of the jumper.
A: (2) Calibrate the analog input curve according to function codes P6.00 to P6.2. For details, refer to the
description of P6 group in Chapter 6 Parameter Description.
VIII. Why was there large deviation on the correspondence relation between the analog output and
the relevant function output?
A: (1) Check if the jumpers of analog output type and control board are properly set. For the analog voltage
output, toggle the corresponding channel to the V end of the jumper; for the analog current output,
toggle the corresponding channel to the I end of the jumper.
A: (2) Calibrate the analog output curve according to function codes P7.05 to P7.09. For details, refer to the
description of P7 group in Chapter 6 Parameter Description.
IX. Why did the inverter report E.AIF analog input abnormal error?
A: (1) Check if the jumpers of analog input type and control board are properly set. For the analog voltage
input, toggle the corresponding channel to the V end of the jumper; for the analog current input, toggle
the corresponding channel to the I end of the jumper.
A: (2) Check if the analog input exceeds 11V;
A: (3) When using the +10V power supply of the inverter control board, check if the voltage of +10V is lower
than 9V or higher than 11V. If yes, check if the resistance value between the +10V and the GND is less
than 1KΩ after the inverter is powered off completely.
X. Why did the inverter report E.P10 abnormal error?
A: Check if the voltage of +10V on the inverter control board is lower than 9V or higher than 11V. If yes,
check if the resistance value between the +10V and the GND is less than 1KΩ after the inverter is
powered off completely.