High Performance Vector Control/Torque Control Inverter User Manual
Chapter 6 Parameter Description 91
6.8 Multi-function Output Parameter (Group P7)
Y1 and relay terminals can be defined as multifunctional digital signal output. AO1 and AO2 terminals
can be defined as multifunctional analog value output, and the analog value type (0 ~ 10V/0 ~ 20mA) can
be selected via the jumper.
The terminal Y2 can act as both multifunctional digital signal output and high-speed pulse output (0 ~
50kHz).
The definition table of multifunctional digital signal output is as follows:
Function setup
Meaning Function setup
Meaning
0
Signal indicating that the inverter is
running (RUN)
1 Frequency arrival signal (FAR)
2
Frequency level det
ection signal
1(FDT1)
3
Frequency level detection signal
2(FDT2)
4
Pre-
warning signal indicating inverter
or motor overload (OL)
5
Stop and lock due to under voltage
(LU)
6 Stop due to external failure (EXT) 7 Frequency upper limit(FHL)
8 Frequency lower limit(FLL) 9 Inverter is running at zero speed
10 Preset counting value action 11 Counting value arrival action
12 Reserved 13
End of Inverter ready for operation
(RDY)
14 Inverter failure 15 Inverter reports alarm
16~18 Reserved 19 Output X1
20 Output X2 21 Reserved
22
Zero current detection arrival (relative
to motor)
23 Stop command indication
24~47 Reserved
0: Signal indicating that the inverter is running (RUN)
The signal is enabled when the inverter is running.
1: Frequency arrival signal (FAR)
When the deviation between the output frequency and the setup frequency of the inverter is in the setup
range of the frequency arrival detection width, the signal is enabled. Refer to P7.19 for details.
2: Frequency level detection signal (FDT1)
When the output frequency of the inverter is higher than FDT1 level upper limit, the signal is enabled.
When the output frequency return to FDT1 level lower limit, the signal is disabled. Refer to P7.20 ~ P7.21
for details.
3: Frequency level detection signal (FDT2)
When the output frequency of the inverter is higher than FDT2 level upper limit, the signal is enabled.
P7.00 Y1 terminal output function selection
0 ~ 47(0)
P7.01 Y2/DO terminal output function selection
0 ~ 71(1)
P7.02 Relay terminal output function selection
0 ~47(14)
P7.03
AO1 terminal output function selection
48~ 71(48)
P7.04 AO2 terminal output function selection
48 ~ 71(49)