Operation manual
1
EWAP400~540MBYNN
Packaged air-cooled water chillers
4PW22679-1B
C
ONTENTS
P
age
Introduction ....................................................................................... 1
Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 1
Important information regarding the refrigerant used ................................ 1
Description ........................................................................................ 2
Function of the main components.............................................................. 3
Safety devices............................................................................................ 3
Internal wiring - Parts table........................................................................ 4
Before operation................................................................................ 5
Checks before initial start-up ..................................................................... 5
Water supply.............................................................................................. 5
Power supply connection and crankcase heating...................................... 5
General recommendations ........................................................................ 5
Operation .......................................................................................... 6
Digital controller......................................................................................... 6
Working with the unit ................................................................................. 6
Advanced features of the digital controller................................................. 9
Troubleshooting............................................................................... 15
Maintenance.................................................................................... 17
Maintenance activities ............................................................................. 17
Disposal requirements............................................................................. 17
I
NTRODUCTION
This operation manual concerns packaged air-cooled water chillers
of the Daikin EWAP-MBYNN series. These units are provided for
outdoor installation and used for cooling applications. The EWAP
units can be combined with Daikin fan coil units or air handling units
for air conditioning purposes. They can also be used for supplying
water for process cooling.
This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local Daikin Dealer.
Technical specifications
(1)
Electrical specifications
(1)
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type: R407C
GWP
(1)
value: 1652.5
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
EWAP400MBYNN
EWAP460MBYNN
EWAP540MBYNN
Packaged air-cooled water chillers
Operation manual
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN
YOUR FILES FOR FUTURE REFERENCE.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Checks before initial
start-up" on page 5.
(1) Refer to the engineering data book for the complete list of specifications.
General EWAP
400 460 540
Refrigerant
R407C
Dimensions HxWxD
(mm)
2250x5901x2238
Weight
machine weight (kg)
4842 4965 5088
operation weight (kg)
4916 5046 5176
Connections
chilled water inlet and outlet
Ø5" (141.3 mm OD)
•evaporator drain
1/4"G
air purge
G 1/2"
Compressor
Type
semi-hermetic single screw
Qty x model
2x
ZHC5WLGUYE
ZHC5WLGUYE +
ZHC7LSGUYE
2x
ZHC7LSGUYE
Speed
(rpm)
2880
Oil type FVC 68D
Oil charge volume
(l)
2x 7.5 7.5 + 10 2x 10
Condensor
Nominal air flow
(m
3
/min)
2880
No. of motors x
output
(W)
12x 1020
Evaporator
Model
2x
AC250EQ-NP96
AC250EQ-NP96 +
AC250EQ-NP128
2x
AC250EQ-NP128
Model EWAP
400 460 540
Power supply
Phase
3~
•Frequency (Hz)
50
•Voltage (V)
400
•Voltage tolerance (%)
±10
Unit
Nominal running current (A)
258 316 373
Maximum running
current
(A)
342 396 452
Recommended fuses
according to IEC 269-2
a) standard (A)
2x (3x 250)
1x (3x 250) +
1 x (3x 300)
2x (3x 300)
b) OP52 (A)
3x 400 3x 425 3x 500
Compressor
Phase
3~
•Frequency (Hz)
50
•Voltage (V)
400
Nominal running current (A)
2x 111
1x 111 + 1x 168
2x 168
Control and fan motor
Phase
3~
•Frequency (Hz)
50
•Voltage (V)
400
Nominal running current (A)
12x 3.1