Daikin EWWD700CJYNN [102/180] Liquid injection

Daikin EWWD480CJYNN [102/180] Liquid injection
Functional Control ESIE07-05
2–64 Part 2 – Functional Description
3
1
2
4
5
2.12 Liquid Injection
Function
description
P When the oil temperature (PT1000; del. temp.) is higher than 85°C (default) the liquid injection will
be activated.
P When the oil temperature decreases to 75% the loquid injection will be disabled.
Liq. Inj. OFF
Liq. Inj. ON
(del Temp.) Oil Temp.
75 C 85 C
Setpoint
Diff.
085 ˚C
10.0 ˚C
Liquid Injection