Daikin EWWD700CJYNN [25/180] Performance factors

Daikin EWWDC11CJYNN [25/180] Performance factors
ESIE07-05 General Outline
Part 1 – System Outline 1–9
3
1
4
5
1.6 Performance Factors
The table below gives the low temperature operation performance factors.
Ethylene glycol/water leaving temperature °C 2 0 -2 -4 -6 -8
Min. % of ethylene glycol 10 20 20 30 30 30
Cooling capacity correction factor 0.842 0.785 0.725 0.670 0.613 0.562
Power input compressors correction factor 0.95 0.94 0.92 0.89 0.87 0.84