Daikin EWLD420I-SS [21/36] Water content in cooling circuits

Daikin EWLD850I-SS [21/36] Water content in cooling circuits
21
Water content in cooling circuits
The cooled water distribution circuits should have minimum water content to avoid excessive compressors start and stop.
In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor sump and simultaneously
there is a rise in the temperature of the compressor motor’s stator due to the inrush current during the start-up.
To prevent damage to the compressors, it has been envisaged the application of a device to limit frequent stops and
restarts.
During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore ensure
that the overall water content allows a more constant functioning of the unit and consequently greater environmental
comfort.
The minimum water content per unit should be calculated using this simplified formula:
For 1 compressor unit
M (liters) = ( 0.94 x ΔT(°C) + 5.87 ) x P(kW)
For 2 compressors unit
M (liters) = ( 0.1595 x ΔT(°C) + 3.0825 ) x P(kW)
For 3 compressors unit
M (liters) = (0.0443 x ΔT(°C) + 1.6202) x P(kW)
where:
M minimum water content per unit expressed in litres
P Cooling Capacity of the unit expressed in kW
ΔT evaporator entering / leaving water temperature difference expressed in °C
This formula is valid for:
- standard microprocessor parameters
For more accurate determination of quantity of water, it is advisable to contact the designer of the plant.

Содержание

Скачать