Daikin EWLD420I-SS [7/36] Supervising systems on request

Daikin EWLD850I-SS [7/36] Supervising systems on request
7
Phase Monitor.
Low pressure ratio.
High oil pressure drop
Low oil pressure.
No pressure change at start.
System security
Phase monitor.
Low Ambient temperature lock-out.
Freeze protection.
Regulation type
Proportional + integral + derivative regulation on the evaporator leaving water output probe.
MicroTech III
MicroTech III built-in terminal has the following features.
164x44 dots liquid crystal display with white back lighting. Supports Unicode fonts for multi-lingual.
Key-pad consisting of 3 keys.
Push’n’Roll control for an increased usability.
Memory to protect the data.
General faults alarm relays.
Password access to modify the setting.
Application security to prevent application tampering or hardware usability with third party applications.
Service report displaying all running hours and general conditions.
Alarm history memory to allow an easy fault analysis.
Supervising systems (on request)
MicroTech III remote control
MicroTech III is able to communicate to BMS (Building Management System) based on the most common protocols as:
ModbusRTU
LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology
BacNet BTP certifief over IP and MS/TP (class 4) (Native)
Chiller Sequencing
MicroTech III controller allows an easy plug-in sequencing technology based on digital or serial panel
Digital Sequencing Panel
This panel is basically a step inserter that switches ON/OFF up to 11 units (chillers or heat pumps operating in the same
cooling/heating mode) depending on the selected set point; the units are connected with the panel through standard cables
and no serial card is requested.
Serial Sequencing Panel
Basically this panel sequences a chiller plant by switching on/off the units (up to 7 chillers) taking into account their running
hours and the requested plant load, in order to optimise the number of working units for each condition; serial cards and
shielded cables are requested to connect the panel with the units and, if installed, a BMS.