Daikin EWAD610TZ-SSB2 [12/104] Options

Daikin EWAD360TZ-SRB1 [12/104] Options

Water filter (opt. code 115– provided as standard for single circuit unit)
The water filter removes impurities fromwater by means of a fine physical barrier (available only on single
circuitunits).
Thefilterisprovidedwitha1,2mmmesh.
Thefilterisshippedloosetogetherwithtwovictaulicjointsandtwocounterpipestobeweldedontheplants.
Opt.115isnotavailablefromfactoryfordualcircuitunits.
NOTE:Theinstallationofthefilterismandatory.
Evaporator flow switch (opt. code 58)
Supplied separately to be wired and installed on the evaporator water piping (by the customer). The
installationoftheflowswitchinmandatory.
Hydronic kits:
-One centrifugal pump (Low lift) (opt. code 78)
-One centrifugal pump (high lift) (opt. code 79)
-Two centrifugal pump (Low lift) (opt. code 80)
-Two centrifugal pump (high lift) (opt. code 81)

Unitmountedhydronickitsareavailablewithsingleanddualpumps.
TheLowliftkitsprovidesanaverageavailableheadof100kPaatchillerstandardconditions.
TheHighliftkitsprovidesanaverageavailableheadof200kPaatchillerstandardconditions.
Thekitiscompletedwithpressuregauge,safetyvalve,drainvalve.Themotorpumpisprotectedbyacircuit
breakerinstalledincontrolpanel.Thekitisassembledandwiredtothecontrolpanel.Thepipeandpumpare
protectedfromfreezingwithanadditionalelectricalheater.
Incaseofunitequippedwithhydronickitonboardselectedtooperatewithglycolmixture,contactfactory.
Inverter kit for pumps:
- INVERTER KIT FOR 1 CENTR PUMP LOW LIFT (opt. code 120e)
-INVERTER KIT FOR 1 CENTR PUMP HIGH LIFT (opt. code 120f)
- INVERTER KIT FOR 2 CENTR PUMP LOW LIFT (opt. code 120g)
- INVERTER KIT FOR 2 CENTR PUMP HIGH LIFT (opt. code 120h)
note:theInverterkitmustbeassociatedwiththecorrespondinghydronickit(opt.code78/79/80/81).

Theinverterkitcanbeusedforthefollowingpurposes:
-Tuning the water flow during unit commissioning.
- Control the pump speed via external input from Builing Management System (BMS)
Forthisapplicationa0-10Vsignalforthepumpspeedmustbeprovidedfromtheplantmanageraccordingto
thespecificcontrolstrategyoftheplant.Thewatermustbewithintheminimumandmaximumvalueallowed
fortheunit(refertothe“Operatinglimit”chapter).Thechangeinwaterflowratemustnotbeexceedmore
than10%ofthedesignwaterflowrateperminute.
- Set a “thermostat off” pump speed. Providing the unit with the inverter kit for the on-board pump is
possible to manage two different water flow settings. A setting for water flow during the "Thermostat ON"
mode (when the chiller is actually providing cooling to the plant), and a set for the “thermostat off” mode
(when the plant load is satisfied and the compressors are waiting to start). This feature allows to achieve
energysavingonplantoperatingcostbyreducingthe speedofthepumpswhenthechillerhasreachedthe
setpoint.
Thankstothesavingonpumpingcost,thepaybacktimefortheInverterKitisapproximatelyoneyear.
12/104