Daikin EWAD610TZ-SSB2 [22/104] Ewad tz sl b

Daikin EWAD610TZ-SSB2 [22/104] Ewad tz sl b
EWAD~TZ-SL B
6"
mm
Evaporatorwaterinlet/outlet
PIPING CONNECTIONS
2
No.
N.ofcircuits
90
kg
Refrigerantcharge
R134a
Refrigeranttype
REFRIGERANT CIRCUIT
77
dB(A)
SoundPressurelevel@1mdistance-
Cooling
98.5
dB(A)
SoundPower-Cooling***
SOUND LEVEL
2
No.
Quantity
20.0
l
Oilcharge
Inverter
DrivenSingle
Screw
Type
COMPRESSOR
11.2
kW
Motorinput
700
rpm
Speed
14
No.
Quantity
52883
l/s
Nominalairflow
800
mm
Diameter
On/Off
Drive*
DPT
Type*
FAN
MCH
Type*
AIR HEAT EXCHANGER
CC
Insulationmaterial*
36.0
kPa
Waterpressuredrop**
33.5
l/s
Waterflowrate
255
l
WaterVolume
S&T
Type*
WATER HEAT EXCHANGER
5359
kg
OperatingWeight
5104
kg
UnitWeight
WEIGHT
6783
mm
Length
2258
mm
Width
2483
mm
Height
DIMENSIONS
GPSS
Material*
IW
Colour*
CASING
5.39
IPLV
4.89
ESEER
2.81
EER
249
kW
Unitpowerinput-Cooling
12
%
Capacitycontrol-Minimumcapacity
Stepless
Capacitycontrol-Type
700
kW
Capacity-Cooling
COOLING PERFORMANCE
EWAD700TZ
-SL B2
MODEL
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient
35.0°C, unit at full load operation; operating f
luid: Water
; fouling factor = 0.
(*) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; CC:
Closed Cell; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter - BRS: Brushless
(**) The value referes to the pressur drop in the evaporator only.
(***) Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are mesuared in accordance with ISO 9614 and Eurovent 8/1
for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and
are for information only and not cosidered binding. The minimum capacity indicated is referred to unit operating at standard Eurovent conditons.
Dimensions and weights are for indication only and not considered binding. Before desining the installation, consult the offical drawings available from the
factory at request. All the data are referred to standard unit without options. Data are subject to change without notice.