Daikin EWAD610TZ-SSB2 [51/104] Electrical specifications

Daikin EWAD610TZ-SSB2 [51/104] Electrical specifications
EWAD~TZ-XR B
INV
INV
INV
INV
INV
INV
Startingmethod
204
190
177
164
151
133
A
Maximumrunningcurrent
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
3
3
3
3
3
3
No.
Phases
COMPRESSORS
41.6
36.4
31.2
31.2
31.2
26
A
Nominalrunningcurrentcooling
FANS
489
453
418
389
361
305
A
Maximumcurrentforwiressizing
450
417
385
358
333
292
A
Maximumrunningcurrent
389
391
393
385
373
231
A
Nominalrunningcurrentcooling
321
300
275
256
237
211
A
Maximumstartingcurrent
UNIT
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
50
50
50
50
50
50
Hz
Frequency
3
3
3
3
3
3
No.
Phases
POWER SUPPLY
EWAD660TZ
-XR B2
EWAD610TZ
-XR B2
EWAD570TZ
-XR B2
EWAD540TZ
-XR B2
EWAD450TZ
-XR B2
EWAD420TZ
-XR B2
MODEL
INV
INV
INV
INV
INV
INV
Startingmethod
115
204
177
151
133
115
A
Maximumrunningcurrent
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
3
3
3
3
3
3
No.
Phases
COMPRESSORS
26
20.8
20.8
15.6
15.6
15.6
A
Nominalrunningcurrentcooling
FANS
276
245
214
180
155
141
A
Maximumcurrentforwiressizing
256
225
198
166
149
130
A
Maximumrunningcurrent
226
192
186
186
113
110
A
Nominalrunningcurrentcooling
184
137
118
101
89
77
A
Maximumstartingcurrent
UNIT
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
50
50
50
50
50
50
Hz
Frequency
3
3
3
3
3
3
No.
Phases
POWER SUPPLY
EWAD360TZ
-XR B2
EWAD320TZ
-XR B1
EWAD290TZ
-XR B1
EWAD240TZ
-XR B1
EWAD220TZ
-XR B1
EWAD190TZ
-XR B1
MODEL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Plese refer to unit nameplate data.
51/104
ELECTRICAL SPECIFICATIONS