INSTALLATION NOTES
For single chiller installation in proximity of a wall the following indications are recommended:
-
if h < Hc L must at least 3 m
-
if h ≥ Hc or L < 3 m contact local Daikin representative to evaluate possible arrangements
In case of two chillers installed side by side in free filed, the minimum distance recommended between the
chillers is indicated in the below picture
In case of two chillers installed in a compound contact local Daikin representative to evaluate possible
arrangements.
For mutliple chiller installation it is recommended to install the chillers is a single row as hown in the below
picture
For additional information refer to the Installation Manual.
If the site does not allow this kind of installation contact Daikin representative to evaluate possible
arrangements.