Daikin EWAH980TZ-SSB2 [60/102] Ewah tz xlb

Daikin EWAH980TZ-SSB2 [60/102] Ewah tz xlb
59/100
SOUND LEVELS
EWAH~TZ-XLB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
180
73.5
69.5
72.5
62.5
55.5
47.5
73
92
220
74.0
70.0
73.0
63.0
56.0
48.0
73
93
270
77.1
74.1
77.1
67.1
59.1
52.1
77
96
300
76.8
73.8
76.8
66.8
58.8
51.8
77
97
350
74.2
71.2
74.2
64.2
56.2
49.2
74
95
390
74.4
71.4
74.4
64.4
56.4
49.4
75
95
430
74.4
71.4
74.4
64.4
56.4
49.4
75
96
480
75.2
72.2
75.2
65.2
57.2
50.2
75
97
580
78.8
75.8
78.8
68.8
60.8
53.8
79
99
620
78.3
75.3
78.3
68.3
60.3
53.3
78
100
670
78.0
75.0
78.0
68.0
60.0
53.0
78
100
710
77.7
74.7
77.7
67.7
59.7
52.7
78
100
760
77.5
74.5
77.5
67.5
59.5
52.5
78
100
820
60.6
69.4
77.1
68.7
60.6
53.2
77
99
930
61.4
70.2
77.9
69.5
61.4
54.0
78
100
990
62.1
70.9
78.6
70.2
62.1
54.7
78
101
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.