OPERATING LIMITS
Heat recovery Units may be optionally equipped with heat recovery system. This system is made by a water
cooled heat exchanger located on the compressors discharge pipe and a dedicated management of condensing
pressure.
To guarantee compressor operation within its envelope, units with heat recovery cannot operate with water
temperature of the heat recovery water lower than 25°C.
It is a responsibility of plant designer and chiller installer to guarantee the respect of this value (e.g. using
recirculating bypass valve).
Water treatment Before putting the unit into operation, clean the water circuit. Dirt, scales, corrosion debris
and other material can accumulate inside the heat exchanger and reduce its heat exchanging capacity. Pressure
drop can increase as well, thus reducing water flow. Proper water treatment therefore reduces the risk of
corrosion, erosion, scaling, etc.. The most appropriate water treatment must be determined locally, according to
the type of system and water characteristics. The manufacturer is not responsible for damage to or malfunctioning
of equipment caused by failure to treat water or by improperly treated water.