Daikin EWAH980TZ-SSB2 [64/102] Ewah tz prb

Daikin EWAH330TZ-SSB1 [64/102] Ewah tz prb
63/100
OPTIONS
EWAH~TZ-PRB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
370
70.8
67.8
70.8
65.8
60.8
52.8
45.8
92
71
440
70.7
67.7
70.7
65.7
60.7
52.7
45.7
93
71
530
73.6
70.6
73.6
67.6
63.6
55.6
48.6
95
73
610
74.1
71.1
74.1
68.1
64.1
56.1
49.1
96
74
690
74.1
71.1
74.1
68.1
64.1
56.1
49.1
96
74
770
55.9
64.7
72.4
66.0
64.0
55.9
48.5
95
72
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.