Electrical data
EWWD-
EJYNN
Maximum
Current for
wires
sizing
Maximum
Starting
Current
(a)
Power
factor at
nominal
conditions
Main
Switch
Short
Circuit
Current
Maximum
Compressor
Current
Circuit 1
Maximum
Compressor
Current
Circuit 2
Maximum
Compressor
Current
Circuit 3
Compressor
Inrush
Current
Circuit 1
Compressor
Inrush
Current
Circuit 2
Compressor
Inrush
Current
Circuit 3
Compressor
Fuse Circuit
1
Compressor
Fuse Circuit
2
Compressor
Fuse Circuit
3
Control
Transformer
Control
Circuit
Breaker
340 215 303 0.88 400 A 25 kA 195 - - 303 - - 250A gG - - 500 VA 4A
400 266 464 0.86 400 A 25 kA 242 - - 464 - - 315A gG - - 500 VA 4A
460 310 464 0.88 400 A 25 kA 282 - - 464 - - 315A gG - - 500 VA 4A
550 353 464 0.90 400 A 25 kA 321 - - 464 - - 355A gG - - 500 VA 4A
650 429 452 0.87 630 A 25 kA 195 195 - 303 303 - 250A gG 250A gG - 500 VA 4A
700 481 614 0.86 630 A 25 kA 195 242 - 303 464 - 250A gG 315A gG - 500 VA 4A
800 532 644 0.86 630 A 25 kA 242 242 - 464 464 - 315A gG 315A gG - 500 VA 4A
850 576 673 0.87 630 A 25 kA 242 282 - 464 464 - 315A gG 315A gG - 500 VA 4A
900 620 673 0.88 800 A 25 kA 282 282 - 464 464 - 315A gG 315A gG - 500 VA 4A
950 663 703 0.89 800 A 25 kA 282 321 - 464 464 - 315A gG 355A gG - 500 VA 4A
C10 706 702 0.89 800 A 25 kA 321 321 - 464 464 - 355A gG 355A gG - 500 VA 4A
C12 799 643 0.86 1000 A 25 kA 242 242 242 464 464 464 315A gG 315A gG 315A gG 1000 VA 8A
C13 843 643 0.86 1000 A 25 kA 242 242 282 464 464 464 315A gG 315A gG 315A gG 1000 VA 8A
C14 887 672 0.87 1000 A 25 kA 242 282 282 464 464 464 315A gG 315A gG 315A gG 1000 VA 8A
C15 931 672 0.88 1250 A 25 kA 282 282 282 464 464 464 315A gG 315A gG 315A gG 1000 VA 8A
C16 974 672 0.88 1250 A 25 kA 282 282 321 464 464 464 315A gG 315A gG 355A gG 1000 VA 8A
C17 1016 702 0.89 1250 A 25 kA 282 321 321 464 464 464 315A gG 355A gG 355A gG 1000 VA 8A
C18 1059 702 0.89 1250 A 25 kA 321 321 321 464 464 464 355A gG 355A gG 355A gG 1000 VA 8A
EWWD -
EJYNN/A
Massima
corrente
per dim.
cavi
Maximum
Starting
Current
(a)
Power
factor at
nominal
conditions
Main
Switch
Short
Circuit
Current
Maximum
Compressor
Current
Circuit 1
Maximum
Compressor
Current
Circuit 2
Maximum
Compressor
Current
Circuit 3
Compressor
Inrush
Current
Circuit 1
Compressor
Inrush
Current
Circuit 2
Compressor
Inrush
Current
Circuit 3
Compressor
Fuse Circuit
1
Compressor
Fuse Circuit
2
Compressor
Fuse Circuit
3
Control
Transformer
Control
Circuit
Breaker
360 215 303 0.88 400 A 25 kA 195 - - 303 - - 250A gG - - 500 VA 4A
440 266 464 0.86 400 A 25 kA 242 - - 464 - - 315A gG - - 500 VA 4A
500 310 464 0.88 400 A 25 kA 282 - - 464 - - 315A gG - - 500 VA 4A
600 353 464 0.90 400 A 25 kA 321 - - 464 - - 355A gG - - 500 VA 4A
750 429 452 0.87 630 A 25 kA 195 195 - 303 303 - 250A gG 250A gG - 500 VA 4A
800 481 614 0.86 630 A 25 kA 195 242 - 303 464 - 250A gG 315A gG - 500 VA 4A
850 532 644 0.86 630 A 25 kA 242 242 - 464 464 - 315A gG 315A gG - 500 VA 4A
950 576 673 0.87 630 A 25 kA 242 282 - 464 464 - 315A gG 315A gG - 500 VA 4A
C10 620 673 0.88 800 A 25 kA 282 282 - 464 464 - 315A gG 315A gG - 500 VA 4A
C11 663 703 0.89 800 A 25 kA 282 321 - 464 464 - 315A gG 355A gG - 500 VA 4A
C12 706 702 0.89 800 A 25 kA 321 321 - 464 464 464 355A gG 355A gG - 500 VA 4A