MEAN WELL ERDN20-24 [2/5] A enclosed type redundancy module

MEAN WELL ERDN20-48 [2/5] A enclosed type redundancy module
File Name:ERDN20-SPEC 2019-11-01
1. All parameters NOT specially mentioned are measured at normal input (5V/12V/24V/48V) , rated load and 25 of ambient temperature.
2. Derating may be needed over high . Please check the derating curve for more details. temperatureambient
3. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude ℃℃
higher than 2000m(6500ft).
4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with
the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
20A Enclosed Type Redundancy Module
SPECIFICATION
MODEL
DC VOLTAGE RANGE
RATED CURRENT
VOLTAGE DROP (Vin-Vout) (max.)
INPUT
EFFICIENCY (Typ.)
OUTPUT
SAFETY STANDARDS
WORKING TEMP.
Note.2
WORKING HUMIDITY
STORAGE TEMP.
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
ENVIRONMENT
SAFETY &
EMC
(Note.4)
PROTECTION
PEAK CURRENT
FUNCTION
RATED CURRENT
DC NORMAL VOLTAGE
SHORT CIRCUIT
PEAK CURRENT (max.)
INPUT REVERSE CURRENT (max.)
INPUT REVERSE VOLTAGE (max.)
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Conducted
Radiated
Harmonic Current
Standard
Standard
EN55032(CISPR32)
EN55032(CISPR32)
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
Test Level / Note
Test Level / Note
Class B
Class B
-----
EMC IMMUNITY
EMC EMISSION
EN55035, EN61000-6-2(EN50082-2), EN55024
Level 4, 15KV air ; Level 3, 8KV contact; criteria A
Level 3, 10V/m ; criteria A
Level 4, 30A/m ; criteria A
Level 3, 10V ; criteria A
Level 3, 2KV ; criteria A
ERDN20-
Voltage Flicker
<30A, 5Sec. No damage
-----
-----
Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-Chassis ;criteria A
OPERATING ALTITUDE Note.3
<30A, 5Sec. No damage
LED STATUS DISPLAY
REDUNDANCY
IEC62368-1, UL62368-1, approvedEAC TP TC 004
NUMBER OF INPUT
2 Channels
CAPACITANCE(Typ.)
STANDBY POWER LOSSES(Typ.)
COOLING
RELAY
BOTH INPUTS VOLTAGE ALARM
=5V, 12V, 24V, 48V
-----
0.206Kg;45psc/10.3Kg/0.81CUFT
618.15K hrs min. Telcordia SR-332 (Bellcore) ; 378.72K hrs min. MIL-HDBK-217F (25 )
65Vdc
0.2V
97%
98%
98%
±℃ 0.03%/ (0 ~ 60 )
-40 ~ +85
12Vdc5Vdc
24Vdc 48Vdc
<4V or >6.5V ( 5 )%± <8.5V or >14.7V ( 5 )%± <34.2V or >63V ( 5 )%±<18V or >31V ( 5 )%±
Скачать