Daikin EWWH405DZXEA1 [20/47] About this chiller

Daikin EWWH470DZXEA2 [20/47] About this chiller
D-EOMWC01405-18EN
20/47
EWWD_DZ EWWH_DZ
HP Sw Test C#1
Off
On, Off. Enables to check operation of the high pressure switch on
#1.
HP Sw Test C#2
Off
On, Off. Enables to check operation of the high pressure switch on
#2.
Ext Fault Cfg=
N/A
Event, Alarm
Definition of the unit behavior after switching of external alarm
contact
4.11.2 Calibrate Sensors
Setpoint/Sub-Menu
Default
Range
Description
Unit
-
Submenu for Unit calibrate sensor
Circuit #1
-
Submenu for Circuit 1 calibrate sensor
Circuit #2
-
Submenu for Circuit 2 calibrate sensor
4.11.2.1 Unit Calibrate Sensors
This page allows a proper calibration of the unit sensors
Setpoint/Sub-Menu
Default
Range
Description
Evap LWT=
7.0°C
Evaporator LWT current reading (includes the offset)
Evp LWT Offset=
0.0°C
Evaporator LWT calibration
Evap EWT=
12.0°C
Evaporator EWT current reading (includes the offset)
Evp EWT Offset=
0.0°C
Evaporator EWT calibration
Evap Pressure=
Evaporator Refrigerant Pressure
Evp Pr Offset=
0.0kPa
Evaporator Refrigerant Pressure Offset
Cond Pressure=
Condenser Refrigerant Pressure
Cnd Pr Offset=
0.0kPa
Condenser Refrigerant Pressure Offset
Common LWT
8°C
Common LWT current reading Includes the offset
Comm LWT Offset=
0.0°C
Common LWT calibration
4.11.2.2 Compressor Calibrate Sensors
This page allows to adjust the sensors and transducers readings.
Setpoint/Sub-Menu
Default
Range
Description
Suction Temp=
Suction Temperature current reading (includes the offset)
Suction Offset=
0.0°C
Suction Temperature offset
Econ Pressure=
Economizer Pressure current reading (includes the offset)
Eco Pr Offset=
0.0kPa
Economizer Pressure offset
Econ Temp=
Economizer Temperature current reading (includes the offset)
Eco Tmp Offset=
0.0°C
Economizer Temperature offset
Calibrations of the Evaporator Pressure and Suction Temperature are mandatory for the applications with
negative water temperature setpoints. These calibrations have to be performed with proper gauge and
thermometer.
An improper calibration of the two instruments may generate limitation of the operations, alarms and even
damages to components.
4.11.3 Scheduled Maintenance
This page may contains the contact number of the Service organization taking care of this unit and the next maintenance
visit schedule.
Setpoint/Sub-Menu
Default
Range
Description
Next Maint=
Jan 2015
Schedule date for next maintenance
Support Reference=
999-999-999
Reference number or email of Service Org
4.12 About this Chiller
This page resumes all the information needed to identify the unit and the current software version installed. These
information may be required in case of alarms or unit failure
Setpoint/Sub-Menu
Default
Range
Description
Model
Unit model and code name
Unit S/N=
Unit serial number
OV14-00001
BSP Ver=
Firmware version