Daikin EWWH455DZXSA2 [18/47] Evaporator lwt

Daikin EWWH490DZXEA2 [18/47] Evaporator lwt
D-EOMWC01405-18EN
18/47
EWWD_DZ EWWH_DZ
Max LWT=
15.0°C
10.0…20.0°C
High limit for Cool LWT1 and Cool LWT2
Min LWT=
-8.0°C
-15.0…-8.0°C
Low limit for Cool LWT1 and Cool LWT2
HR EWT Stp=
N/A
30.0…50.0°C
Heat Recovery Entering Water Setpoint
HR EWT Dif=
N/A
1.0…10.0°C
Heat Recovery Water Temperature differential
4.4 Evaporator LWT
This link jumps to the page “Temperatures”. This page resumes all the relevant water temperatures.
Setpoint/Sub-Menu
Range
Description
Evap LWT=
-
Controlled water temperature
Evap EWT=
-
Return water temperature
Cond LWT=
-
Condenser leaving water temperature
Cond EWT=
-
Condenser entering water temperature
Evap Delta T=
-
Delta T across Evaporator
Cond Delta T=
-
Delta T across Condenser
Pulldn Rate
-
Rate of decrease of the controlled temperature
Ev LWT Slope
-
Rate of decrease of the controlled temperature
Cd LWT Slope
-
Rate of decrease of the condenser leaving water temperature
Outside Air=
-
Outside air temperature
Act Slope Lim.
Maximum slopes
Switch Box T=
-
Switch Box temperature
Common LWT=
-
Master Slave Common supply water temperature
HR LWT=
-
Heat Recovery Leaving Water Temperature
HR EWT=
-
Heat Recovery Entering Water Temperature
4.5 Condenser LWT
This link jumps to the page “Temperatures”. See section 4.4 for detailed page content.
4.6 Unit Capacity
This page displays the actual unit and circuit capacity
Setpoint/Sub-Menu
Default
Range
Description
Unit=
-
-
Actual unit capacity
Circuit #1=
-
-
Actual circuit 1 capacity
Circuit #2=
-
-
Actual circuit 2 capacity
4.7 Unit Mode
This item shows the present Operating Mode and jumps to the page for unit mode selection.
Setpoint/Sub-Menu
Default
Range
Description
TZ / TZ B
VZ
Available Modes=
Cool
Cool,
Cool w/ Glycol,
Cool/Ice w/ Glycol,
Ice w/ Glycol,
Test
Cool,
Cool w/ Glycol,
Cool/Ice w/ Glycol,
Ice w/ Glycol,
Heat/Cool,
Heat/Cool w/Glycol,
Heat/Ice w/Glycol,
Pursuit,
Test
Available operating modes
Depending on selected mode among availables, the Unit Mode on the main menu will assume the corresponding value
according to the following table:
Available mode selected
Operating Mode
TZ/TZ B
VZ
C/H Switch = Cool
C/H Switch = Heat
Cool
Cool
Cool
N/A
Cool w/ Glycol
Cool/Ice w/ Glycol
Ice w/ Glycol
Ice
Ice
Heat/Cool
N/A
Cool
Heat
Heat/Cool w/Glycol
Heat/Ice w/Glycol
Ice
Pursuit
Pursuit
Test
Test
Test
4.8 Unit Enable
This page allows to enable or disable unit and circuits. For the unit it also possible enable the operation with time scheduler,
while for circuit it is possible to enable the test mode.