MEAN WELL MSP-1000-12 [2/6] Series
![MEAN WELL MSP-1000-12 [2/6] Series](/views2/1678012/page2/bg2.png)
μμ
SPECIFICATION
MSP-1000-12 MSP-1000-15 MSP-1000-24 MSP-1000-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.) Note.2
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
SAFETY &
FUNCTION
EMC
(Note 8)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
12V 15V 24V 48V
80A 64A 42A 21A
0 ~ 80A 0 ~ 64A 0 ~ 42A 0 ~ 21A
960W (max. 1000W for 3 sec.) 960W (max. 1000W for 3 sec.) 1008W 1008W
150mVp-p 150mVp-p 200mVp-p 250mVp-p
11 ~ 14V 14 ~ 17V 22 ~ 28V 46 ~ 56V
±2.0% ±1.5% ±1.0% ±1.0%
±0.5% ±0.5% ±0.5% ±0.5%
±2.0% ±1.5% ±0.5% ±0.5%
1000ms, 50ms/230VAC 2000ms, 50ms/115VAC at full load
16ms/230VAC 16ms/115VAC at full load
90 ~ 264VAC(300VAC for 5 sec.) 127 ~ 370VDC
47 ~ 63Hz
PF>0.95/230VAC PF>0.98/115VAC at full load
14.5 ~ 16.5V 18.2 ~ 20.6V 29 ~ 33V 58 ~ 65V
91.5% 92% 93% 94%
8.5A/115VAC 5A/230VAC
20A/115VAC 40A/230VAC
105 ~ 135% rated output power
Protection type :
Constant current limiting, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
ANSI/AAMI ES60601-1, IEC60601-1 ; CAN/CSA-C22.2 No.60601-1:14-Edition 3 approved
I/P-O/P:4.5KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
-40 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
286.3K hrs min. Telcordia SR-332 (Bellcore) ; 105.7K hrs min. MIL-HDBK-217F (25 )℃
218*105*63.5mm (L*W*H)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the derating curve for more details.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. No load power consumption<0.75W when RC+ & RC- (CN100 pin3,4) open.
7. When the input voltage is less than 40VAC, the SPS may exhibit degradation of performance. The final product manufacturers must re-confirm this
deviation that does not affect basic safety or essential performance.
8. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 700 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
9. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
1.53Kg;8pcs/13.3Kg/1.34CUFT
5V STANDBY
5VSB : 5V@0.3A ; tolerance 5%, ripple : 50mVp-p(max.)±
FAN CONTROL
Fan on/off by NTC(RT50) or 30% load min.
Earth leakage current < 360 A/264VAC , Touch leakage current < 100 A/264VAC
ISOLATION LEVEL
Primary-Secondary: 2×MO P, Primary-Earth: 1×MO P, Secondary-Earth: 1×MO PPP P
1000W Single Output Medical Type
MSP-1000 series
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Class B
Class B
Class A
-----
EMC IMMUNITY
EMC EMISSION
EN60601-1-2
Level 4, 15KV air ; Level 4, 8KV contact
Level 3
Level 3
Level 4, 2KV/Line-Line 4KV/Line-Earth
Level 3
Level 4
100% dip 1 periods, 30% dip 25 periods,
100% interruptions 250 periods
CURRENT SHARING
Up to 4000W or (3+1) units. Please refer to the Function Manual.
DC-OK SIGNAL
REMOTE ON-OFF CONTROL
Power ON : short; Power OFF : open. Please refer to the Function Manual.
The TTL signal out, PSU turn on = 3.3 ~ 5.6V ; PSU turn off = 0 ~ 1V. Please refer to the Function Manual.
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual.
File Name:MSP-1000-SPEC 2018-09-21
Содержание
- Msp 100 1
- Series 1
- Msp 100 2
- Series 2
- Specification 2
- W single output medical type 2
- Block diagram 3
- Derating curve output derating vs input voltage 3
- Msp 100 3
- Series 3
- W single output medical type 3
- Function description of cn100 4
- Function manual 4
- Msp 100 4
- Series 4
- W single output medical type 4
- Current sharing 5
- Difference of output voltages among parallel units should be less than 0 v 5
- Maximum output current at parallel operation rated current per unit number of unit 0 5
- Msp 100 5
- Msp 1000 has the built in active current sharing function and can be connected in parallel up to 4 units to provide higher output power as exhibited below 5
- Remote on off control 5
- Series 5
- The power supplies should be paralleled using short and large diameter wiring and then connected to the load 5
- The psu can be turned on off by using the remote control function 5
- The total output current must not exceed the value determined by the following equation 5
- W single output medical type 5
- When the total output current is less than 5 of the total rated current or say 5 of rated current per unit number of unit the current shared among units may not be fully balanced 5
- Installation manual 6
- Mechanical specification mechanical specification 6
- Msp 100 6
- Series 6
- W single output medical type 6
Похожие устройства
- MEAN WELL MSP-1000-12 Документация
- MEAN WELL MSP-1000-15 Инструкция по эксплуатации
- MEAN WELL MSP-1000-15 Инструкция язык EN
- MEAN WELL MSP-1000-15 Data sheet
- MEAN WELL MSP-1000-15 Документация
- MEAN WELL MSP-1000-24 Инструкция по эксплуатации
- MEAN WELL MSP-1000-24 Инструкция язык EN
- MEAN WELL MSP-1000-24 Data sheet
- MEAN WELL MSP-1000-24 Документация
- MEAN WELL MSP-1000-48 Инструкция по эксплуатации
- MEAN WELL MSP-1000-48 Инструкция язык EN
- MEAN WELL MSP-1000-48 Data sheet
- MEAN WELL MSP-1000-48 Документация
- MEAN WELL MSP-100-12 Инструкция по эксплуатации
- MEAN WELL MSP-100-12 Инструкция язык EN
- MEAN WELL MSP-100-12 Data sheet
- MEAN WELL MSP-100-12 Документация
- MEAN WELL MSP-100-15 Инструкция по эксплуатации
- MEAN WELL MSP-100-15 Инструкция язык EN
- MEAN WELL MSP-100-15 Data sheet