MEAN WELL RKP-1UT-CMU1 [3/6] Rkp 1u rack system

MEAN WELL RKP-1UT-CMU1 [3/6] Rkp 1u rack system
JK1 IN/OUT Connector pins function description
CN500 Pin No. Assignment
JK1 Pin No. Assignment
CN500 IN/OUT Connector pins function description
Pin No.
1,2
3
4
5
7
8
6
Function
DA,DB
-V
CONTROL
NC
SCL
GND-AUX
SDA
Description
Differential digital signal for parallel control. (Note.1)
Negative output voltage. For parallel control, can't be connected directly to the load.
Remote ON/OFF control pin used in the PMBus interface. (Note.2)
Not use.
Serial Data used in the PMBus interface. (Note.2)
Serial Clock used in the PMBus interface. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note.1: Non-isolated signal, referenced to the output terminals (-V).
Note.2: Isolated signal, referenced to GND-AUX.
Pin No. Function
Description
1,7,16
2,8,17
3,9,18
4,10,19
5,11,20
13
24
14
6,12,21
ON/OFF
AC-OK
DC-OK
PV
T-ALARM
FAN FAIL
+V
+12V-AUX
+5V-AUX
15
22
GND-AUX
+S
23 -S
25 -V
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No. Pin No. Pin No. Pin No. Pin No.
2
1
3
4
5
Assignment Assignment Assignment Assignment Assignment
AC-OK-A
ON/OFF-A
DC-OK-A
PV-A
T-ALARM-A
7
13
9
8
10
14
15
6
12
11 16
17
23
21
22
25
18
19
20
24
AC-OK-B
DC-OK-B
PV-B
ON/OFF-B
FAN FAIL-A
FAN FAIL-B
+5V-AUX
+12V-AUX
GND-AUX
T-ALARM-B ON/OFF-C
AC-OK-C
DC-OK-C -S
FAN FAIL-C
+S
-V
PV-C
T-ALARM-C
+V
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B,C(pin 1,7,16) and
+5V-AUX(pin 13). Short: ON, Open:OFF. (Note.2)
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
High : When the Vout 80 5%. Low : When Vout 80 5%. ± ± (Note.2)
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND- (pin 15). The maximum load current is 0.3A. This output has the AUX
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Positive output voltage. For local sense use only, can't be connected directly to the load.
Negative output voltage. For local sense use only, can't be connected directly to the load.
Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND- (pin 15). The maximum load current is 0.8A. This output has theAUX
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Connector Pin No. Assignment(CN ) : RJ45 8 positions
Pin No. Pin No. Pin No.
2 5
1 4
3 6
Assignment Assignment Assignment
DA CONTROL
-V
NC
SDA
DB
7
8
SCL
GND-AUX
File Name:RKP-1U RACK SYSTEM-SPEC
2015-02-11
RKP-1U Ra ck Sys te m
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
2000~6000W Front End Power System