MEAN WELL RKP-1UT-CMU1 [6/6] Rkp 1u rack system

MEAN WELL RKP-1UT-CMU1 [6/6] Rkp 1u rack system
Command
Code
# of data
Bytes
Description
Command
Name
Transaction
Type
99h
9Ah
9Bh
9Ch
9Dh
9Eh
12
12
6
3
6
12
Manufacturer's name
Manufacturer's model name
Firmware revision
Manufacturer's factory location
Manufacture date. (format: YYMMDD)
Product serial number
MFR_ID
MFR_MODEL
MFR_REVISION
MFR_LOCATION
MFR_DATE
MFR_SERIAL
Block Read
Block Read
Block Read
Block R/W
Block R/W
Block R/W
90h
91h
98h
2
2
1
Fan speed 1 reading value
(format: Linear, N= 4)
Fan speed 2 reading value
(format: Linear, N= 4)
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
READ_FAN_SPEED_1
READ_FAN_SPEED_2
PMBUS_REVISION
R Word
R Word
R Byte
81h
80h
88h
8Bh
8Ch
1
1
2
2
2
Fan1 and 2 status reporting
Manufacture specific status reporting
AC input voltage reading value
(format: Linear, N=-1)
Output voltage reading value
(format: Linear, N= -9)
Output current reading value
(format: Linear, N= -3)
STATUS_FANS_1_2
STATUS_MFR_SPECIFIC
READ_VIN
READ_VOUT
READ_IOUT
R Byte
R Byte
R Word
R Word
R Word
8Dh 2
Temperature 1 reading value
(format: Linear, N= -3)
READ_TEMPERATURE_1 R Word
File Name:RKP-1U RACK SYSTE M-SPEC
201 5-02-11
2000~6000W Front End Power System
RKP-1U Ra ck Sys tem

Содержание

Скачать