SPECIFICATION
10000W Power Supply with Single Output
RST-10000 series
File Name:RST-10000-SPEC 2019-07-16
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
ALARM SIGNAL OUTPUT
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD(OLP)
OVER VOLTAGE
AC CURRENT (Typ.)
2200ms, 80ms at full load
20ms / 230VAC at 75% load 14ms / 230VAC at full load
3 3-wire / 196 ~ 305VAC or 3 4-wire / Y 340 ~ 530VACψ△ ψ
47 ~ 63Hz
30A/230VAC( ) 18A/400VAC( / Y)
3 3-wire / 3 4-wireψ△ ψ
150A/230VAC( ) 100A/400VAC( / Y)3 3-wire / 3 4-wireψ△ ψ
<7mA / 305VAC(Y 530VAC)△
100 ~ 112% rated output power
User selectable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")℃
AC fail, DC OK, fan fail, OTP. Please refer to the Function Manual.
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
50K hrs min. Telcordia SR-332 (Bellcore) ; 17K hrs min. MIL-HDBK-217F (25 )℃
540*424*83.5mm (L*W*H)
23.5Kg; 1pcs/23.5Kg/2.82CUFT
88.5% 90.5%89.5%
1. All parameters NOT specially mentioned are measured at 230VAC(Y 400VAC) input, rated load and 25 of ambient temperature.△ ℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. During withstand voltage and isolation resistance testing, the screw A shall be temporarily removed, and shall be installed back after the testing.
5. There is high possibility to trigger the floating over voltage protection when PV voltage is trimmed from a high voltage level to a lower voltage level at light
load or no load condition. It is suggested that turn off the power supply and set PV voltage to the lowest level, then adjust output voltage to a desired value.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.1300 900 2 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
POWER FACTOR (Typ.) 0.95/230VAC(400VAC) at full load
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
WITHSTAND VOLTAGE Note.4
ISOLATION RESISTANCE
Note.4
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 6)
PROTECTION
Shut down o/p voltage, recovers automatically after temperature goes down
30 ~ 33.6V 60 ~ 67.2V45 ~ 50.4V
±0.5% ±0.5%±0.5%
±0.5% ±0.5%±0.5%
±1.0%
Can be adjusted via built-in potentiometer
±1.0%±1.0%
150mVp-p
23.5 ~ 28.8V
200mVp-p200mVp-p
47 ~ 57.6V35 ~ 43.2V
24V
400A
0 ~ 400A
9600W
48V36V
210A276A
0 ~ 210A0 ~ 276A
10080W9936W
RST-10000-24 RST-10000-48RST-10000-36
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual.
REMOTE ON-OFF CONTROL
AUXILIARY POWER
CURRENT SHARING
By electrical signal or dry contact Power ON:open Power OFF:short. Please refer to the Function Manual.
12V@0.1A(Only for Remote ON/OFF control)
Up to 20000W or (1+1) units. Please refer to the Function Manual.
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class A
Class A
-----
-----
EMC IMMUNITY
EMC EMISSION
CONSTANT CURRENT LEVEL PROGRAMMABLE
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Adjustment of output voltage is allowable to between 20 ~ 120% of nominal output voltage. Please refer to the Function Manual.
Adjustment of constant current level is allowable to between 20 ~ 100% of rated current. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
Содержание
- Rst 1000 1
- Series 1
- Rst 1000 2
- Series 2
- Specification 2
- W power supply with single output 2
- Block diagram 3
- Derating curve 3
- Efficiency vs load 48v model 3
- Rst 1000 3
- Series 3
- Static characteristics 3
- W power supply with single output 3
- Ac power connection 4
- Function manual 4
- Rst 1000 4
- Series 4
- W power supply with single output 4
- 1 by potentiometer svr 5
- 2 by output voltage programming 5
- A have the dip switch position 3 set as 5
- B output voltage can be trimmed by svr 5
- B the output voltage can be trimmed to 20 120 of the nominal voltage by applying external voltage between and on cn992 or cn993 pv pv 5
- Or pv remote voltage programming remote adjust margin programming dynamic voltage trim 5
- Rst 1000 5
- S and v as well as s and v need to be connected as factory default setting 5
- Series 5
- Voltage adjustment 5
- W power supply with single output 5
- 1 default overload protection olp value 6
- 2 by constant current level programming a have the dip switch position 2 set as 6
- A have the dip switch position 2 set as b output current is set default value 6
- Current adjustment 6
- Or pc remote current programming dynamic current trim 6
- Rst 1000 6
- S and v as well as s and v need to be connected as factory default setting 6
- Series 6
- W power supply with single output 6
- Rst 1000 7
- Rst 10000 7
- Series 7
- W power supply with single output 7
- Rst 1000 8
- Series 8
- W power supply with single output 8
- 1 kgf cm 0 9
- 5mm m4 9
- Connection for output current programming 9
- Connection for output voltage programming 9
- Hole no recommended screw size max penetration depth l recommended mounting torque 9
- Hrs df11 10ds or equivalent 9
- Hrs df11 sc or equivalent 9
- Mating housing 9
- Mechanical specification 9
- Mounting screw 9
- Mounting surface chassis of rst 10000 9
- Negative sensing for remote sense 9
- Positive sensing for remote sense 9
- Rst 1000 9
- Series 9
- Terminal 9
- W power supply with single output 9
- Installation manual 10
- Rst 1000 10
- Series 10
- W power supply with single output 10
Похожие устройства
- MEAN WELL RST-10000-24 Каталог
- Сибконтакт ИС2-12-300Г4 Руководство по эксплуатации
- MEAN WELL RST-10000-36 Инструкция по эксплуатации
- MEAN WELL RST-10000-36 Инструкция язык en
- MEAN WELL RST-10000-36 Каталог
- Сибконтакт ИС2-12-300П Руководство по эксплуатации
- MEAN WELL RST-10000-36 Data Sheet
- Сибконтакт ИС2-110-300 Руководство по эксплуатации
- MEAN WELL RST-10000-48 Инструкция по эксплуатации
- MEAN WELL RST-10000-48 Инструкция язык en
- MEAN WELL RST-10000-48 Каталог
- MEAN WELL RST-10000-48 Data Sheet
- Сибконтакт ИС2-60-300М2 Руководство по эксплуатации
- MEAN WELL RST-5000-24 Инструкция по эксплуатации
- MEAN WELL RST-5000-24 Инструкция язык en
- MEAN WELL RST-5000-24 Каталог
- Сибконтакт ИС2-60-300 Руководство по эксплуатации
- MEAN WELL RST-5000-24 Data Sheet
- Сибконтакт ИС2-55-300 Руководство по эксплуатации
- MEAN WELL RST-5000-36 Инструкция по эксплуатации