MEAN WELL RST-5000-24 [2/10] Rst 500
![MEAN WELL RST-5000-24 [2/10] Rst 500](/views2/1681428/page2/bg2.png)
SPECIFICATION
5000W Single Output Power Supply
RST-5000 series
File Name:RST-5000-SPEC 2019-07-29
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
2200ms, 80ms at full load
20ms / 230VAC at 75% load 14ms / 230VAC at full load
3 3-wire / 196 ~ 305VAC or 3 4-wire / Y 340 ~ 530VACψ△ ψ
47 ~ 63Hz
15A/230VAC( ) 9A/400VAC( / Y)
3 3-wire / 3 4-wireψ△ ψ
75A/230VAC( ) 50A/400VAC( / Y)3 3-wire / 3 4-wireψ△ ψ
<3.5mA / 305VAC(Y 530VAC)△
100 ~ 112% rated output power
User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
30 ~ 33.6V 60 ~ 67.2V45 ~ 50.4V
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
44.1K hrs min. Telcordia SR-332 (Bellcore) ; 34.6K hrs min. MIL-HDBK-217F (25 )℃
460*211*83.5mm (L*W*H)
10Kg; 1pcs/10.1Kg/0.85CUFT
88.5% 90.5%89.5%
±0.5% ±0.5%±0.5%
±0.5% ±0.5%±0.5%
±1.0% ±1.0%±1.0%
150mVp-p
23.5 ~ 28.8V
200mVp-p200mVp-p
47 ~ 57.6V35 ~ 43.2V
24V
200A
0 ~ 200A
4800W
48V36V
105A138A
0 ~ 105A0 ~ 138A
5040W4968W
RST-5000-24 RST-5000-48RST-5000-36
1. All parameters NOT specially mentioned are measured at 230VAC(Y 400VAC) input, rated load and 25 of ambient temperature.△ ℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. During withstand voltage and isolation resistance testing, the screw A shall be temporarily removed, and shall be installed back after the testing.
5. There is high possibility to trigger the floating over voltage protection when PV voltage is trimmed from a high voltage level to a lower voltage level at light
load or no load condition. It is suggested that turn off the power supply and set PV voltage to the lowest level, then adjust output voltage to a desired value.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.720 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
POWER FACTOR (Typ.) 0.95/230VAC(400VAC) at full load
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
WITHSTAND VOLTAGE Note.4
ISOLATION RESISTANCE
Note.4
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 6)
PROTECTION
Shut down o/p voltage, recovers automatically after temperature goes down
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class A
Class A
-----
-----
EMC IMMUNITY
EMC EMISSION
ALARM SIGNAL OUTPUT
REMOTE ON-OFF CONTROL
AUXILIARY POWER(AUX)
Please refer to the Function Manual.
AC fail, DC OK, fan fail, OTP. Please refer to the Function Manual.
12V@0.1A(Only for Remote ON-OFF control)
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual.
CURRENT SHARING
Up to 20000W or (3+1) units. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
Can be adjusted via built-in potentiometer
Adjustment of output voltage is allowable to between 20 ~ 120% of nominal output voltage. Please refer to the Function Manual.
Adjustment of constant current level is allowable to between 20 ~ 100% of rated current. Please refer to the Function Manual.
CONSTANT CURRENT LEVEL PROGRAMMABLE
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Содержание
- Rst 500 1
- Series 1
- Rst 500 2
- Series 2
- Specification 2
- W single output power supply 2
- Block diagram 3
- Derating curve 3
- Efficiency vs load 48v model 3
- Rst 500 3
- Series 3
- Static characteristics 3
- W single output power supply 3
- Ac power connection 4
- Function manual 4
- Rst 500 4
- Series 4
- W single output power supply 4
- 1 by potentiometer svr 5
- 2 by output voltage programming 5
- A have the dip switch position 3 set as 5
- B output voltage can be trimmed by svr 5
- B the output voltage can be trimmed to 20 120 of the nominal voltage by applying external voltage between and on cn313 or cn314 pv pv 5
- Or pv remote voltage programming remote adjust margin programming dynamic voltage trim 5
- Rst 500 5
- S and v as well as s and v need to be connected as factory default setting 5
- Series 5
- Voltage adjustment 5
- W single output power supply 5
- 1 default overload protection olp value 6
- 2 by constant current level programming a have the dip switch position 2 set as 6
- A have the dip switch position 2 set as b output current is set default value 6
- Current adjustment 6
- Or pc remote current programming dynamic current trim 6
- Rst 500 6
- S and v as well as s and v need to be connected as factory default setting 6
- Series 6
- W single output power supply 6
- Rst 500 7
- Rst 5000 7
- Series 7
- W single output power supply 7
- Current sharing 8
- Rst 500 8
- Rst 5000 has the built in active current sharing function and can be connected in parallel up to 4 units to provide higher output power as exhibited below the voltage difference among each output should be minimized that less than 0 v is required the total output current must not exceed the value determined by the following equation maximum output current at parallel operation the rated current per unit x number of unit x0 when the total output current is less than 5 of the total rated current or say 5 of rated current per unit number of unit the current shared among units may not be fully balanced 8
- S s and cs cs and rc rc are connected mutually in parallel when the remote sense function is used in parallel operation the sensing wire must be connected only to the master unit wires of the remote sense function should be kept at least 30 cm from input wires 8
- Series 8
- W single output power supply 8
- 1 kgf cm 0 9
- 5mm m4 9
- Air flow direction 9
- Connection for output current programming 9
- Connection for output voltage programming 9
- File name rst 5000 spec 2019 07 29 9
- Hole no recommended screw size max penetration depth l recommended mounting torque 9
- Hrs df11 10ds or equivalent 9
- Hrs df11 sc or equivalent 9
- M3 ψ 8 9
- M4 l 5mm 9
- Mating housing 9
- Mechanical specification 9
- Mounting screw 9
- Mounting surface chassis of rst 5000 9
- Negative sensing for remote sense 9
- Positive sensing for remote sense 9
- Rst 500 9
- Screw a 9
- Series 9
- Terminal 9
- W single output power supply 9
- Installation manual 10
- Rst 500 10
- Series 10
- W single output power supply 10
Похожие устройства
- Сибконтакт ИС2-55-300 Руководство по эксплуатации
- MEAN WELL RST-5000-36 Инструкция по эксплуатации
- MEAN WELL RST-5000-36 Инструкция язык en
- MEAN WELL RST-5000-36 Каталог
- MEAN WELL RST-5000-36 Data Sheet
- MEAN WELL RST-5000-48 Инструкция по эксплуатации
- MEAN WELL RST-5000-48 Инструкция язык en
- MEAN WELL RST-5000-48 Каталог
- MEAN WELL RST-5000-48 Data Sheet
- MEAN WELL RT-125A Инструкция по эксплуатации
- MEAN WELL RT-125A Инструкция язык en
- MEAN WELL RT-125A Каталог
- MEAN WELL RT-125A Data Sheet
- MEAN WELL RT-125B Инструкция по эксплуатации
- MEAN WELL RT-125B Инструкция язык en
- MEAN WELL RT-125B Каталог
- MEAN WELL RT-125B Data Sheet
- MEAN WELL RT-125C Инструкция по эксплуатации
- MEAN WELL RT-125C Инструкция язык en
- MEAN WELL RT-125C Каталог