Daikin FWL02DAT [227/280] Fwecsa

Daikin FWL02DAT [227/280] Fwecsa
RU
9
РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ
строжайше запрещено воспроизведение, даже частичное, этого руководства
FC66003946
Вер. 00
Панель управления для терминалов
FWECSA
МЕНЮ НАСТРОЙКИ
ОПИСАНИЕ
ПО
УМОЛЧАНИЮ
Minimum cooling SET limit 10.0 °C
Maximum cooling SET limit 35.0 °C
Minimum heating SET limit 5.0 °C
Maximum heating SET limit 30.0 °C
Minimum humidity SET limit 35%
Maximum humidity SET limit 75%
Humidity hysteresis 5%
Offset on humidity reading 0%
Minimum value of modulating ventilation 20%
Maximum value of modulating ventilation 100%
Air probe offset 0.0 °C
Water probe offset 0.0 °C
Heating water probe offset 0.0 °C
Economy Hysteresis 2.5 °C
Cooling water consent SET 22.0 °C
Cooling water consent hysteresis 5.0 °C
Heating water consent SET 30.0 °C
Heating water consent hysteresis 7.0 °C
Dehumidification water consent SET 10.0 °C
Dehumidification water consent hysteresis 2.0°C
Valve water consent SET 30 °C
Valve water consent hysteresis 5.0 °C
Heater water consent SET 39.0 °C
Heater water consent hysteresis 2.0 °C
Temperature minimum control SET 9.0 °C
Temperature minimum control hysteresis 1.0 °C
Neutral zone 5.0 °C
Default values RESET No
МЕНЮ ЗАДАННЫХ ПАРАМЕТРОВ
На главной странице дисплея, нажимая на кнопки ВВЕРХ/ВНИЗ, в
последовательности открываются следующие страницы:
• Подключение автономного режима
• Подключение использования электрического нагревательного
элемента
• Подключение контроля минимальной температуры
• Подключение контроля влажности
• Уставка влажности
Если невозможно перейти к модификации одной или нескольких
опций, необходимо заранее установить соответствующие параметры
конфигурации. Например, для подключения использования
электрического нагревательного элемента, необходимо заранее
установить его наличие в параметрах конфигурации.