Daikin UATY09KTAL [35/87] Cooling capacity 60hz

Daikin UATY09KTAL [35/87] Cooling capacity 60hz
Capacity Tables ED43-441
34 Packaged Air Conditioners UATY-K Series
7.3 Cooling Capacity [60Hz]
UATY06KTAL
UATY06KYAL
UATY08KTAL
UATY08KYAL
(m³/min.)
(˚CWB)
(˚CDB)
(kW)
(kW)
(kW)
Symbols:
AFR
BF
EWB
EDB
TC
SHC
PI
: Air flow rate
: Bypass factor
: Entering wet bulb temp.
: Entering dry bulb temp.
: Total cooling capacity
: Sensible heat capacity
: Power input
(Comp.+outdoor fan motor).
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2. shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02×AFR×(1-BF)×(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.
3D014895A
AFR(BF)
47
(0.15)
52
(0.16)
62
(0.18)
EWB(˚C)
14.0
16.0
18.0
19.0
19.5
22.0
24.0
14.0
16.0
18.0
19.0
19.5
22.0
24.0
14.0
16.0
18.0
19.0
19.5
22.0
24.0
EDB(˚C)
20.0
22.0
25.0
27.0
27.0
30.0
32.0
20.0
22.0
25.0
27.0
27.0
30.0
32.0
20.0
22.0
25.0
27.0
27.0
30.0
32.0
TC
15.8
16.9
17.9
18.5
18.8
20.3
21.5
16.1
17.2
18.3
18.9
19.2
20.7
21.9
16.6
17.7
18.9
19.4
19.7
21.3
22.6
SHC
11.8
11.9
12.6
13.2
12.9
13.1
13.1
12.3
12.4
13.1
13.8
13.4
13.7
13.6
13.1
13.2
14.0
14.7
14.4
14.7
14.7
PI
5.4
5.5
5.6
5.7
5.7
5.9
6.1
5.4
5.6
5.7
5.8
5.8
6.0
6.1
5.5
5.6
5.8
5.8
5.9
6.0
6.2
TC
15.2
16.2
17.3
17.8
18.1
19.5
20.7
15.5
16.5
17.6
18.1
18.4
19.9
21.1
16.0
17.0
18.1
18.7
19.0
20.4
21.7
SHC
11.5
11.5
12.2
12.8
12.5
12.8
12.7
11.9
12.0
12.7
13.4
13.0
13.3
13.2
12.7
12.8
13.5
14.3
14.0
14.3
14.3
PI
5.9
6.0
6.1
6.2
6.2
6.4
6.6
5.9
6.0
6.2
6.2
6.3
6.5
6.6
6.0
6.1
6.2
6.3
6.4
6.5
6.7
TC
14.6
15.6
16.6
17.1
17.4
18.8
19.9
14.9
15.9
16.9
17.4
17.7
19.1
20.2
15.3
16.3
17.4
17.9
18.2
19.6
20.8
SHC
11.1
11.2
11.8
13.0
12.1
12.4
12.4
11.6
11.6
12.3
13.0
12.6
13.0
12.9
12.3
12.4
13.2
13.9
13.6
13.9
13.9
PI
6.4
6.5
6.7
6.7
6.8
7.0
7.1
6.4
6.6
6.7
6.8
6.8
7.0
7.2
6.5
6.6
6.8
6.8
6.9
7.1
7.2
TC
13.9
14.9
15.8
16.3
16.6
17.9
19.0
14.2
15.1
16.1
16.6
16.9
18.2
19.3
14.5
15.5
16.5
17.0
17.3
18.7
19.8
SHC
10.7
10.8
11.4
12.1
11.7
12.0
12.0
11.1
11.2
11.9
12.6
12.2
12.5
12.5
11.8
11.9
12.7
13.5
13.1
13.5
13.4
PI
6.9
7.1
7.2
7.3
7.3
7.5
7.7
7.0
7.1
7.2
7.3
7.4
7.6
7.7
7.0
7.2
7.3
7.4
7.4
7.6
7.8
TC
13.2
14.1
15.0
15.5
15.7
17.0
18.0
13.4
14.3
15.2
15.7
16.0
17.2
18.3
13.8
14.7
15.6
16.1
16.4
17.7
18.7
SHC
10.3
10.3
11.0
11.6
11.3
11.6
11.5
10.7
10.7
11.4
12.1
11.8
12.1
12.1
11.4
11.5
12.3
13.0
12.6
13.0
13.0
PI
7.5
7.7
7.8
7.9
7.9
8.1
8.3
7.5
7.7
7.8
7.9
8.0
8.2
8.3
7.6
7.8
7.9
8.0
8.0
8.2
8.4
TC
12.4
13.2
14.1
14.6
14.8
16.0
12.6
13.4
14.3
14.8
15.0
16.2
12.9
13.8
14.7
15.1
15.4
16.6
SHC
9.8
9.9
10.5
11.2
10.9
11.2
10.2
10.3
11.0
11.6
11.3
11.7
10.9
11.0
11.7
12.5
12.1
12.5
PI
8.1
8.3
8.4
8.5
8.6
8.8
8.2
8.3
8.5
8.6
8.6
8.8
8.2
8.4
8.5
8.6
8.7
8.9
TC
12.0
12.9
13.7
14.1
14.4
15.6
12.2
13.1
13.9
14.4
14.6
15.8
12.5
13.4
14.3
14.7
15.0
16.2
SHC
9.6
9.7
10.3
11.0
10.7
11.0
10.0
10.1
10.8
11.4
11.1
11.5
10.7
11.0
11.5
12.3
11.9
12.3
PI
8.4
8.5
8.7
8.8
8.9
9.0
8.4
8.6
8.7
8.8
8.9
9.1
8.5
8.6
8.8
8.9
8.9
9.1
25 30 35 40 45 50 52
Indoor air
Outdoor temp. (˚CDB)
(m³/min.)
(˚CWB)
(˚CDB)
(kW)
(kW)
(kW)
Symbols:
AFR
BF
EWB
EDB
TC
SHC
PI
: Air flow rate
: Bypass factor
: Entering wet bulb temp.
: Entering dry bulb temp.
: Total cooling capacity
: Sensible heat capacity
: Power input
(Comp.+outdoor fan motor).
3D014899A
Notes:
1. Direct interpolation is permissible.
Do not extrapolate beyond the Operation Limits.
2. shows nominal capacities.
3. SHC is based on each EWB and EDB.
SHC*=SHC correction for other dry bulb. (DB*)
=0.02×AFR×(1-BF)×(DB*-EDB)
Add SHC* to SHC.
4. Above cooling capacities do not include indoor fan motor heat.