Daikin FXMQ80MVE [188/254] Malfunction of transmission between centralized remote controller and indoor unit

Daikin FXM40LVE [188/254] Malfunction of transmission between centralized remote controller and indoor unit
Si38-606 Troubleshooting by Indication on the Remote Controller
Troubleshooting 177
2.50
UE
Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
Failure of PC board for centralized remote controller
Defect of indoor unit PC board