150 Troubleshooting
3.23 J3 Outdoor Unit: Malfunction of Discharge Pipe
Thermistor (R2T)
Remote
Controller
Display
J3
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R2T) for outdoor unit discharge pipe
Defect of outdoor unit PC board (A1P)
Troubleshooting
Refer to thermistor resistance / temperature characteristics table on P224.
(V3072)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
R2T from the outdoor
unit PC board.
(5.0k~
640k)
Replace outdoor unit PC board
(A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R2T).
YES
YES
Connector
is connected to
X12A of outdoor unit
PC board
(A1P).