Daikin FXAQ50MAVE [62/264] Stopping operation

Daikin FXAQ20MAVET [62/264] Stopping operation
SiBE34-703 Special Control
Function 51
3.6 Stopping Operation
Operation of the actuator when the system is down, is cleared up.
3.6.1 When System is in Stop Mode
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV3) 0 pls
Hot gas bypass valve (SVP)
OFF
Ending conditions Indoor unit thermostat is turned ON.

Содержание