SiBE311209 Field Setting
Test Operation 164
3.2.3 Setting by DIP Switches
<Outdoor Units>
Using DIP switches on the PCB enables field setting shown below. However, make no changes
of factory settings except for DS1-1.
Setting at replacement by spare PCB
Refer “DS1-1~4, DS2-1~4 setting detail” on next page.
DIP switch
Setting item Description
No. Setting
DS1-1
~DS1-4
ON
Not used Do not change the factory settings.
OFF (Factory setting)
DS2-1
~4
ON
Not used Do not change the factory settings.
OFF (Factory setting)
Caution
DIP switch setting after changing the main PCB (A1P) to spare PCB.
After the replacement by the spare PCB, be sure to make settings shown below.
When you change the main PCB (A1P) to spare PCB, please carry out the following setting.
DIP Switch Detail
DS No. Item Contents
DS1-1
ON
Do not change the factory settings.
OFF
(Factory
setting of spare
PCB)
DS1-2 Power supply
specification
ON 200V class (220V)
OFF
(Factory
setting of spare
PCB)
400V class (380V)
DS1-3 ON Do not change the factory settings.
OFF
(Factory
setting of spare
PCB)
DS1-4 Unit allocation
setting
ON
Make the following settings according to allocation of
unit. (All models are set to OFF at factory.)
DS2-1
OFF (Factory
setting of spare
PCB)
DS2-2 Model setting
DS2-3
DS2-4
Initial conditions of DIP switches
ON
OFF
ON
OFF
1 2 3 4 1 2 3 4
DS1 DS2
Make the following settings according to models of outdoor units.
(All models are set to OFF at factory.)
RTSQ8PA RTSQ10PA RTSQ12PA RTSQ14PA RTSQ16PA
DS2-2 OFF ON OFF ON OFF
DS2-3 ON ON OFF OFF ON
DS2-4OFFOFFONONON
Domestic
Japan
Overseas
General
Europe
DS1-4
OFF OFF ON
DS2-1
OFF ON OFF