Daikin FXSQ125PVE4 [94/370] Restart standby

Daikin FXSQ100PVE [94/370] Restart standby
Standby SiBE311209
85 Function
3. Standby
3.1 Restart Standby
This function is used to forcedly turn OFF the thermostat for a period of 2 minutes after a compressor stops running, in
order to prevent the frequent ON-OFF operations of the compressor and equalize pressure in the refrigerant circuit.
Furthermore, the outdoor unit fan continues residual operation for a while to facilitate pressure equalization and prevent
the stay of refrigerant in evaporator.
3.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Actuator
Symbol
Electric
symbol
Operation
RTSQ8PA RTSQ10 · 12PA RTSQ14 · 16PA
Compressor 1 M1C OFF OFF OFF
Compressor 2 M2C OFF OFF
Compressor 3 M3C OFF
Outdoor unit fan1 MF1
Ta > 30°C: STEP4
Ta 30°C: OFF
Ta > 30°C: STEP4
Ta 30°C: OFF
Ta > 30°C: STEP4
Ta 30°C: OFF
Outdoor unit fan2 MF2
Ta > 30°C: STEP4
Ta 30°C: OFF
Electronic expansion valve
(Main)
EVM Y1E 0 pls
Electronic expansion valve
(Subcooling)
EVT Y3E 0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ Y2E 80 pls
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG Y1S OFF
Four way valve (Heat
exchanger switch)
20SA Y3S Holds
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL Y4S OFF
Solenoid valve (Hot gas) SVP Y5S OFF
Solenoid valve (Main bypass)
SVE Y6S OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO Y7S OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT Y8S OFF
Solenoid valve (Heat
exchanger hot gas)
SVHG Y9S OFF
Four way valve (High/low
pressure gas pipe switch)
20SB Y2S Holds
Ending conditions 2 min.
Crankcase heater
OFF
Discharge pipe
temperature < 70°C
Discharge pipe
temperature > 75°C
Crankcase heater
ON