Troubleshooting by Indication on the Remote Controller SiBE311209
295 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor unit main
PCB.
Confirmation of
error 3
Confirmation of
error 4
YES
NO
YES
NO
Diagnosis Flow 1
Confirmation of
error 3
Confirmation of
error 4
Diagnosis Flow 2
The number of indoor
units connected to the
same refrigerant circuit
system should not be
more than 64 units.
The number of indoor units
exceeds the standard. Check the
connection to correct.
Check if the refrigerant
type of the outdoor unit
corresponds to that of the
indoor unit.
Replace the outdoor unit main
PCB.
With single systems, replace the
control PCB 1 (A1P).
With multi systems, replace the
outdoor unit main PCB (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.